the Class 2 conductors are to be installed in the 
wallbox with the power conductors. Use 
approved connectors (supplied by others) to 
make Class 2 connections inside the wallbox. 

Inner Sections of Multiganged Switches 

REMOVE INNER SECTIONS

DO NOT REMOVE OUTER SECTIONS

 

• 

CAUTION

:  TO REDUCE THE RISK OF 

OVERHEATING AND POSSIBLE DAMAGE 
TO OTHER EQUIPMENT, DO NOT INSTALL 
TO CONTROL A RECEPTACLE. 

• 

Wiring: Use copper wire only. For supply 
connection, use wires rated for at least 75°C. 

• 

Load Type: The -SW, -SWS, and -SLVS are 
designed for use with permanently installed 
incandescent, fluorescent (non-dimmable), low 
voltage, neon/cold cathode, HID, general 
purpose fan, or tungsten halogen lighting. 

• 

Temperature: The -SW, -SWS, and -SLVS are 
designed to be used where temperatures are 
between 32° to 104°F (0° to 40°C). 

The load capacity must also be derated. The following 
charts provide derating information for various 
applications. 

• 

Wallboxes: Devices mount in standard 
wallboxes. For easy installation, Crestron 
recommends using 3 ½” deep wallboxes. Several 
devices can be installed in one wall box 
(multigang). This requires the removal of side 
sections (refer to diagram on page 3) and the 
derating of the switching device. For a smooth 
appearance, one-piece multigang faceplates (not 
supplied) can be installed. 

Derating Information for Incandescent, Tungsten Halogen, 
and Electronic Low Voltage Applications 

Part Number

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW 1000W 

 600W  400W 

-SWS 

1000W  

600W 

400W 

-SLVS 

No Derating Necessary 

Derating Information for Magnetic Low Voltage and 
Neon/Cold Cathode Applications

*

 

• 

Other Switch Devices: Mechanical 3- or 4-way 
switches will not work with the -SW, -SWS, or  
-SLVS. 

Part 

Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW 

1000VA/750W 600VA/450W  400VA/300W 

-SWS 

1000VA/750W 

600VA/450W 

400VA/300W 

-SLVS 

No Derating Necessary 

• 

Spacing: If mounting one device above another, 
leave at least 4 ½” vertical space between them. 

*  VA ratings are for input power to the transformer. If you do not 

know the input power requirement of the transformer, use the bulb’s 
wattage rating to determine proper rating. 

Multigang Installations 

In multigang installations, several controls are grouped 
horizontally in one wallbox. For a smooth appearance, 
one-piece multigang faceplates (not supplied) can be 
installed. 

Derating Information for Fluorescent/HID Applications 

Part 

Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW 

8A 5A  3A 

-SWS 

8A 

5A 

3A 

-SLVS 

No Derating Necessary 

1.  When combining controls in a wallbox, remove 

inner side sections prior to wiring (refer to the 
following figure). 

Derating Information for General Purpose Fans 

Part 

Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW 

3A 3A  3A 

-SWS 

3A 

3A 

3A 

-SLVS 

No Derating Necessary 

2.  To remove a side section, bend the side section 

back and forth with a pair of pliers until the 

Installation Guide – DOC. 6134B 

Stand Alone Wall Box Switch:  CLW-SW, SWS, & SLVS  