Crestron CLTI-2DIMU8 Installation Manual Download Page 2

TROUBLE 

POSSIBLE CAUSE(S) 

CORRECTIVE ACTION 

The output does not appear 
to dim below 50%. 

The dimmer channel may 
have been damaged. 

Contact Crestron 
customer service. 

The connected LED load 
buzzes and flickers when 

dimmed. 

An incompatible LED 

fixture is installed. 

Verify the connected LED 
load is dimmable and has 
been tested. Refer to 
Crestron’s Light Fixture 
Compatibility Listing at 
www.crestron.com/ 
resources/lighting-fixture-

compatibility. 

An incorrect dimming 
phase is selected. 

Set the dimming phase to 
Auto or Reverse Phase 
mode to reduce current 

spikes to load. 

The connected LED load 
flickers or turns off when 

dimmed to a low level. 

The minimum dimming 

level is set too low. 

Adjust the minimum 
dimming level to match 
the minimum level 

required by the LED load. 

The LED load does not dim 
to a low brightness level. 

An incorrect dimming 
phase is selected. 

Set the dimming phase to 
Forward Phase mode. 

 

As of the date of manufacture, these products have been tested and found to comply with 
specifications for CE marking.

The product warranty can be found at www.crestron.com/warranty.
The specific patents that cover Crestron products are listed at patents.crestron.com.
Certain Crestron products contain open source software. For specific information, please visit 
www.crestron.com/opensource.
Crestron, the Crestron logo, Cresnet, and Crestron Toolbox are either trademarks or registered 
trademarks of Crestron Electronics, Inc. in the United States and/or other countries. UL is either a 
trademarks or registered trademarks of Underwriters Laboratories, Inc. in the United States and/or 
other countries. Other trademarks, registered trademarks, and trade names may be used in this 
document to refer to either the entities claiming the marks and names or their products. 

Crestron Electronics, Inc. 

Installation Guide - DOC. 7851B

15 Volvo Drive   Rockleigh, NJ 07647 

(2047970)

Tel: 888.CRESTRON 

01.17

Fax: 201.767.7576  

Specifications subject to 

www.crestron.com 

change without notice.

Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible 
for errors in typography or photography.
This document was written by the Technical Publications department at Crestron.
©2017 Crestron Electronics, Inc.

Wiring the Terminal Block to the Feed and Load(s) (Right-Side Double-Wide Enclosures)

LINE 1

Connection from a 

15 or 20 A circuit 

breaker

Bypass 

jumpers

Terminal 

block

To loads

Right-side 

wiring label

LINE 2

Connection from a 

15 or 20 A circuit 

breaker

Ground 

bus

Module 

location 

label

NEUTRAL

NEUTRAL

GND

CLX-2DIMU8

DIM 8
DIM 7
DIM 6
DIM 5

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

N OUT 8
N OUT 7
N OUT 6
N OUT 5
N IN 2

DIM 5

LINE 2

DIM 4
DIM 3
DIM 2
DIM 1

LINE 1

N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN 1

Module interconnect 

cable attached

Connection not 

made

Controlling Local Loads and Setting Load Type

Use Local mode to verify that each load is connected to the proper output on the modules. 
Refer to the illustration that follows for button locations.
  1.  Press the 

SETUP 

button to enter Local mode. Output 1 turns full on.

  2.  Press the mode button to cycle through the dimming modes, and press the 

SETUP 

button to save the setting and advance to the next output. The dimming mode is 
identified by the blinking LED.

 

●  Green indicates forced reverse phase.

 

●  Red indicates forced forward phase.

 

●  Yellow and green indicate auto-select reverse phase.

 

●  Yellow and red indicate auto-select forward phase.

 

●  Red and green indicate non-dim.

  3.  Press the 

SETUP 

button to advance to output 2. Repeat step 2 for the remaining 

outputs.

  4.  After turning on the last output, press the 

SETUP 

button again to turn on all outputs 

and verify that they are operating correctly.

  5.  Press the 

SETUP 

button to turn off all outputs and LEDs and exit Local mode.

NOTE

:  Adjustment to the dimming mode locally is disabled if the dimming phase is 

set in the SIMPL program.

CLXI-2DIMU8 Mode and SETUP Button Locations

Setup button

Mode button

Brown from breaker

Brown from breaker

Blue from panel or 

breaker

Red to loads

Red to loads

Blue to loads

Blue to loads

CLX-2DIMU8

DIM 1
DIM 2
DIM 3
DIM 4

DIM 5
DIM 6
DIM 7
DIM 8

N IN 1

N OUT 1
N OUT 2
N OUT 3
N OUT 4

N IN 2

N OUT 5
N OUT 6
N OUT 7
N OUT 8

LINE 1

LINE 2

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

Blue from panel or 

breaker

Brown from breaker

Brown from breaker

Blue from panel or

breaker

Red to loads

Red to loads

Blue to loads

Blue to loads

Blue from panel or

breaker

CLX-2DIMU8

DIM 8
DIM 7
DIM 6
DIM 5

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

N OUT 8
N OUT 7
N OUT 6
N OUT 5
N IN 2

DIM 5

LINE 2

DIM 4
DIM 3
DIM 2
DIM 1

LINE 1

N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN 1

Jumper removed

Jumper installed

Jumper removed

Jumper installed

CLX-2DIMU8

DIM 8
DIM 7
DIM 6
DIM 5

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

N OUT 8
N OUT 7
N OUT 6
N OUT 5
N IN 2

DIM 5

LINE 2

DIM 4
DIM 3
DIM 2
DIM 1

LINE 1

N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN 1

Jumper removed

Jumper installed

Jumper removed

Jumper installed

CLX-2DIMU8

DIM 1
DIM 2
DIM 3
DIM 4

DIM 5
DIM 6
DIM 7
DIM 8

N IN 1

N OUT 1
N OUT 2
N OUT 3
N OUT 4

N IN 2

N OUT 5
N OUT 6
N OUT 7
N OUT 8

LINE 1

LINE 2

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

Troubleshooting

The following table provides corrective actions for possible trouble situations. If further 

assistance is required, please contact a Crestron customer service representative.

The module displays error codes using the dimmer output LEDs. The LED blinks a pattern, 
such as 1-2 or 2-4, to indicate the error on that output. For example, a 1-2 error blinks the 
LED 1 time, pauses for 1 second, blinks two times, pauses for two seconds, and then 
repeats until the error is corrected. A 2-4 error blinks the LED blinks two times, pauses for 
1 second, blinks four times, pauses for two seconds, and then repeats until the error is 
corrected. Refer to the following table for possible corrections.

  5.  Turn on the circuit breakers and verify that the green PWR LED on the module lights, 

the breakers do not trip, and the power is delivered to the loads.

  6.  Turn off the circuit breakers.

NOTE

:  Before removing the bypass jumpers, make sure to properly connect and 

program the control system that provides functionality to the system.

  7.  Remove the bypass jumpers on the brown and red sections of the terminal block. 

The jumpers on the blue sections of the terminal block must remain installed.

Module Installation and Wiring

CAUTION

:  The module contains electrostatic sensitive devices (ESDs); the unit must be 

handled from the metal chassis. Do not touch the PC board or components.

NOTE

:  Install the modules after the enclosure has been completely wired. Refer to 

“Terminal Block Installation and Field Wiring” for details. 

Install and wire the module.
  1.  Turn off the circuit breakers. 
  2.  Use the four supplied self-tapping Phillips pan head screws (8B x 1/4 in length) to 

secure the module to the enclosure.

  3.  Connect the wires from the module to the terminal block. Each wire exits the module 

directly in line with, and is the same color as, the terminal to which it should be 
connected. Wires are prestripped to 12 mm (1/2 in). Tighten to 1 Nm. 

  4.  If the module is being installed above another module within the enclosure, attach 

the supplied module interconnect cable between the two modules. The illustration 
that follows shows the area within a double-wide enclosure where the corners of 
four modules meet. 

NOTE

:  One wire on the module interconnect cable may be a different color from 

the rest. The color has no bearing on its orientation during installation. 

 

Using Module Interconnect Cable to Wire One Module to Another

Wiring the Terminal Block to the Module (Single-Wide and Left-Side Double-Wide Enclosures)

Removing the Line Jumpers after Testing (Single-Wide and Left-Side Double-Wide Enclosures 
and Right-Side Mounted CLTI-2DIMU8 Shown)

Wiring the Terminal Block to the Module (Right-Side Double-Wide Enclosures)

  8.  Turn on the circuit breakers.

NOTE

:  Power must be supplied to LINE 1 for the module to communicate with the 

control system or for any of the circuits to operate.

  9.  If the program is not yet running, test the loads using Local mode.

ERROR 

CODE 

ERROR NAME 

FAULT DESCRIPTION 

1-1 

Master MCU 
Stuck in 

Bootloader 

The firmware upgrade has failed or has been aborted, 
leaving the master processor in bootloader. Reinitiate 

firmware upgrade from Crestron Toolbox software. 

1-2 

Dimming 
Processor 

Unresponsive 

Communications to the corresponding dimming 
processor have failed. Confirm that power is supplied 
to LINE 2/N IN 2. Then reboot the unit or contact 

Crestron customer service. 

1-3 

Dimming 
Processor 
Firmware 

Upgrade Failed 

The firmware upgrade has failed or has been aborted, 
leaving the dimming processor in bootloader. 
Reinitiate the firmware upgrade from Crestron 

Toolbox. 

2-1 

Overcurrent 
Tripped 

A short circuit or overload has been detected and 
output has been switched off.  

 

Check wiring for shorts. 

 

Verify that the total load connected to the 
channel is less than 2.5 A. 

 

Verify that the dimming phase has not been set 
to Forward Phase mode if an incandescent or 
electronic load is connected. 

The channel attempts to resume normal operation 

after receiving another command to turn on. 

2-2 

Shorted FET 

The dimmer channel has failed. Disconnect the load 
and contact Crestron Technical Support. 

2-3 

Overtemperature 
Tripped 

The dimming channel has overheated and shut down 
due to excessive load.  

 

Verify that the total load connected to the 
channel is less than 2.5 A. 

 

Verify that the panel ventilation is not blocked. 

The channel resumes normal operation after cooling. 

2-4 

Overvoltage 
Detected 

High-voltage spikes have been detected and output 
has been shut down. 
If a magnetic load is connected, verify that the 
dimming phase has been set to Forward Phase 

mode.  

3-1 

Zero Cross Fault 

The dimmer is unable to lock onto the ac line. 
If the unit is powered by a generator, verify that 

generator output is 50/60 Hz and stable. 

 

Reviews: