Crestron CLTI-2DIMU8 Installation Manual Download Page 1

CLTI-2DIMU8/CLXI-2DIMU8

Terminal Block and Module
Installation Guide

Description

The Crestron

®

 230 V, 2-Feed, 8-Dimmer Terminal Block and Module (CLTI-2DIMU8 and 

CLXI-2DIMU8) are considered single entities and must be used together. They ship 
separately to permit termination of the field wiring to the terminal block (CLTI) prior to 
installation of the module (CLXI). The terminal block is designed to terminate the circuit 
feed (LINE and NEUTRAL) and distribute the controlled circuit (LOAD) to the fixtures. The 
module connects to the terminal block and performs dimming control of LED, 
incandescent, magnetic low-voltage, or dimmable 2-wire fluorescent lighting loads. 
The maximum load is 2.5 A per channel; the maximum load is 20 A total for the 
CLXI-2DIMU8. The CLXI-2DIMU8 accepts two 10 A feeds that can be different phases.
An oversize heat sink dissipates heat efficiently. There are LEDs on the module to indicate 
communication to a Cresnet

®

 network, input power to the module, and output power to 

the load.
The CLTI terminals and CLXI modules are shown in the following illustrations.

CLTI-2DIMU8 Terminal Block with Left- and Right-Side CLXI-2DIMU8 Labels

Additional Resources

Visit the product page on the Crestron website 
(www.crestron.com) for additional information 
and the latest firmware updates. Use a QR 
reader application on your mobile device to 
scan the QR image.

CLX-2DIMU8

DIM 1
DIM 2
DIM 3
DIM 4

DIM 5
DIM 6
DIM 7
DIM 8

N IN 1

N OUT 1
N OUT 2
N OUT 3
N OUT 4

N IN 2

N OUT 5
N OUT 6
N OUT 7
N OUT 8

LINE 1

LINE 2

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

CLX-2DIMU8

DIM 8
DIM 7
DIM 6
DIM 5

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

N OUT 8
N OUT 7
N OUT 6
N OUT 5
N IN 2

DIM 5

LINE 2

DIM 4
DIM 3
DIM 2
DIM 1

LINE 1

N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN 1

CLXI-2DIMU8 Module (Connects to a CLTI-2DIMU8)

Terminal Block and Module Layout for a Double-Wide Enclosure (CLTI-2DIMU8 and 
CLXI-2DIMU8 Shown)

Ground bus

CLTI- terminal 

block

CLXI- module

Ground bus

CLTI- terminal block

CLTI- terminal block

CLXI- module

CLX-2DIMU8

DIM 8
DIM 7
DIM 6
DIM 5

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

N OUT 8
N OUT 7
N OUT 6
N OUT 5
N IN 2

DIM 5

LINE 2

DIM 4
DIM 3
DIM 2
DIM 1

LINE 1

N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN 1

NOTE

:  Unless otherwise indicated, the lighting system specified in this guide is 

modular, requiring assembly in the field by a licensed electrician in accordance with all 
national and local codes.

If an assembled UL

®

 Listed panel is required, Crestron offers this service through its UL 

Listed panel shop. This includes complete in-factory system configuration and assembly 
by Crestron for an additional fee.

Terminal Block Installation and Field Wiring

Terminal block installation requires installation of the supplied adhesive label and the 
terminal block. The adhesive label provides the labeling for each terminal in the terminal 
block and is designed to accommodate installation into the left or right side of a cabinet. 
Refer to the illustrations that follow for details.

WARNING

:  The CLXI-2DIMU8 may be powered from multiple circuit breakers.

NOTE

:  Both left-side and right-side adhesive wiring labels are provided. The left-side 

labels are used in both single- and double-wide enclosures. The right-side labels are 
used only in double-wide enclosures. 

1.  Remove the backing from the left- or right-side adhesive wiring label.
2.  Apply the adhesive label by aligning the holes in the label with the holes on the 

Crestron Automation Enclosure where the terminal block is to be mounted. The 
wiring label lies beneath the terminal block.

3.  Use the two supplied self-tapping Phillips pan head screws (8B x 1/4 in length) to 

secure the terminal block to the Crestron Automation Enclosure.

CAUTION

:  Bypass jumpers are provided to allow testing of circuits and to protect 

the module during installation. When properly secured by five screws, each of the 
two jumpers on the brown and red sections of the terminal block shorts the line in 
to dim out so that the circuit is energized. Do not remove any bypass jumpers until 
all feed and load wiring has been completed, the circuit has been tested for 
electrical faults, and the module has been installed. Refer to “Module Installation 
and Wiring” for details.

Furthermore, the two jumpers on the blue sections of the terminal block tie the 
neutral ins to the neutral outs. These jumpers should never be removed.

NOTE

:  Use copper conductors only—rated 75 °C or greater.

4.  Turn off the circuit breakers.
5.  Connect the circuit feed (line and neutral) and controlled circuit (load) wires to the 

terminal block per the markings provided on the wiring label. Terminal blocks accept 
one 2.5–6 mm

2

 wire. Strip the wires to 12 mm (1/2 in). Tighten terminal blocks to 

1 Nm. 

6.  Grounding terminal blocks are available in the cabinet for termination of ground 

wires. Tighten to 4 Nm (2.5–6 mm

2

), 4.5 Nm (10 mm

2

), or 5.1 Nm (16–25 mm

2

). 

7.  Test each circuit for electrical faults by turning on each of the circuit breakers and 

checking that the breakers do not trip and that power is delivered to the proper 
loads.

Wiring the Terminal Block to the Feed and Load(s) (Single-Wide and Left-Side Double-Wide 
Enclosures)

LINE 1

Connection from a 

15 or 20 A circuit 

breaker

Bypass 

jumpers

Terminal 

block

To loads

Left-side 

wiring label

LINE 2

Connection from a 

15 or 20 A circuit 

breaker

Ground 

bus

Module 

location 

label

NEUTRAL

NEUTRAL

GND

CLX-2DIMU8

DIM 1
DIM 2
DIM 3
DIM 4

DIM 5
DIM 6
DIM 7
DIM 8

N IN 1

N OUT 1
N OUT 2
N OUT 3
N OUT 4

N IN 2

N OUT 5
N OUT 6
N OUT 7
N OUT 8

LINE 1

LINE 2

2 FEED

8 DIM

120VAC 60 Hz

SINGLE PHASE

16A MAX/FEED

CLTI-2DIMU8

CLXI-2DIMU8

Specifications

Specifications are listed in the table below.

Installation

A licensed electrician must mount the terminal block and module into a Crestron 
Automation Enclosure in accordance with all national and local codes.

CAUTION

:  This equipment is for indoor use only and needs to be air cooled. Mount in a 

well-ventilated area. The ambient temperature must be 10° to 40 °C (32° to 104 °F). The 
relative humidity must be 

1

0% to 90% (noncondensing).

NOTE

:  For 2-feed systems, the two input lines can be different phases.

NOTE

:  When connecting to an arc fault breaker, ensure the load does not exceed 

1,000 W total. Crestron certified breakers have a 2,000 W limit.

IMPORTANT NOTES

: When controlling magnetic low-voltage transformers:

•  Do not use a CLXI-2DIMU8 module for switching or dimming large magnetic 

transformers (>100 VA).

•  Do not connect more than eight magnetic transformers on any one output, regardless 

of lamp wattage. 

•  Do not hot plug transformers or add or remove bypass jumpers while the output 

channel is energized.

•  Do not mix magnetic and electronic transformers on the same output channel.

Failure to follow the guidelines above can lead to damage of the dimmer module and 
transformers.

NOTE

:  Before using the CLXI-2DIMU8, ensure the device is using the latest firmware. 

Check for the latest firmware for the CLXI-2DIMU8 at www.crestron.com/firmware. Load 
the firmware onto the device using Crestron Toolbox™ software.

Install terminal blocks along the left side of single-wide enclosures and along the outside 
edges (left and right sides) of double-wide enclosures. Install modules along the right side 
of single-wide enclosures and side-by-side in the center of double-wide enclosures. When 
installing modules and terminal blocks in a double-wide enclosure, be sure to invert the 
units on the right side so that they can be properly wired. Refer to the illustrations that 
follow when considering the location of terminal blocks and modules within an enclosure.

NOTE

:  Modules and terminal blocks must be installed into the lowest available spaces 

and continue toward the top of the enclosure.

Terminal Block and Module Layout for a Single-Wide Enclosure (CLTI-2DIMU8 and 
CLXI-2DIMU8 Shown)

* When connecting to a third-party arc fault breaker, ensure that the total load does not exceed 1,000 W 

per feed.

SPECIFICATION 

DETAILS 

Load Ratings 

Dimmer Channels 

Per Channel 

2.5 A 

Per Group 

Channels 1–4: 10 A 
Channels 5–8: 10 A 

Module Total 

20 A* 

Minimum Load 

0 A 

Dimming Modes 

Auto-load detection, forced reverse-phase, forced 

forward-phase 

Load Types 

LED, incandescent, magnetic low-voltage, electronic 
low-voltage, 2-wire fluorescent and nondimmable 

lighting 

Power Requirements 

One or two feeds (the same or different phases) 
230 Vac, 50/60 Hz, single-phase 

Environmental 

Temperature 

0° to 40 °C (32° to 104 °F) 

Humidity 

10% to 90% RH (noncondensing) 

Heat Dissipation 

12 Btu/h + (3.8 Btu/h x Load Current in A)  
88 Btu/h at maximum load  

Enclosure 

Gray metal with black heat sink, surface mount 

module with two integral mounting flanges; 
Occupies 1 module space in a CAEN or CAENIB 

enclosure 

Voltage Limit for 

SELV/PELV Circuits 

24 V 