Crestron CLT-2IND Installation Manual Download Page 2

Terminal Block & Module    Crestron 

CLT- & CLX-2IND/4IND

 

Installation and Field Wiring 

Wiring CLX-2IND Terminal Block to the Feed and Load(s) 
for Single-Wide Enclosure and Left Side of Double-Wide 
Enclosure 

1.  Use the two supplied self-tapping pan Phillips 

screws (8B x ¼” length) to secure the terminal 
block and the appropriate (left or right) wiring 
label to the Crestron Automation Enclosure. The 
wiring label lies beneath the terminal block as 
shown on this and the following page. 

FROM DIMMER

TO LOAD

FROM DIMMER

TO LOAD

 

NOTE:

  Both left and right wiring labels are 

provided. The left-side labels are common for both 
single and double-wide enclosures. The right-side 
labels are only used in double-wide enclosures since 
the modules and terminal blocks along the right side 
must be inverted when mounting.  

NOTE:

  Use copper conductors only – rated 75

°

2.  With the circuit breaker turned off, connect the 

dimmer module output (IN) and the load (OUT) 
wires to the IND terminal block per the markings 
provided on the wiring label (as shown in the 
following diagrams). Terminal blocks accept one 
14 - 10 AWG wire. Wires should be stripped to 
½ inch. Tighten terminal blocks to 9 in-lbs.  

3.  Test the circuit for electrical faults by turning on 

the circuit breaker and checking that the breaker 
does not trip and that the proper lighting loads 
are energized.  

Wiring CLX-2IND Terminal Block to the Feed and Load(s) 
for Right Side of Double-Wide Enclosure 

FROM DIMMER

TO LOAD

TO LOAD

FROM DIMMER

 

 

2  

  Terminal Block & Module:  CLT- & CLX-2IND/4IND 

Installation Guide – DOC. 6315 

Summary of Contents for CLT-2IND

Page 1: ... in Double wide Enclosure CLT CLX 4IND shown The terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes TERMINAL BLOCK LEFT MODULES TERMINAL BLOCK RIGHT GROUNDING TERMINAL BLOCKS CAUTION This equipment is for indoor use only Mount in a well ventilated area The ambient temperature must be 32 F to 104 F...

Page 2: ...are only used in double wide enclosures since the modules and terminal blocks along the right side must be inverted when mounting NOTE Use copper conductors only rated 75 C 2 With the circuit breaker turned off connect the dimmer module output IN and the load OUT wires to the IND terminal block per the markings provided on the wiring label as shown in the following diagrams Terminal blocks accept ...

Page 3: ...ule to the terminal block Wires are pre stripped to inch Tighten to 9 in lbs NOTE Each inductor should be wired with one wire connected to an input and the other wire connected to the corresponding output The inductors have no polarity 3 Turn off the circuit breaker and remove the bypass jumpers on the terminal block Refer to following diagrams for a close up of the jumpers Wiring Diagram of the T...

Page 4: ...nty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any If you cannot locate specific information or have questions after reviewing this guide please take advantage of Crestron s award winning customer service team by calling the Crestron corporate headquarters ...

Reviews: