Terminal Block & Module
Crestron
CLT- & CLX-1FAN4
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Single-wide and Left Side Double-wide Enclosures)
NOTE:
Unless otherwise indicated, the lighting
system specified in this guide is modular, requiring
assembly in the field by a licensed electrician, in
accordance with all national and local codes.
TERMINAL
BLOCK
N OUT 2
GROUNDING
TERMINAL
BLOCK
GND
CRESTRON
LEFT SIDE
WIRING LABEL
TO
LOAD(S)
AREA FOR
MODULE
LOCATION
LABEL
N OUT 3
N OUT 4
(FROM 15 OR 20 AMP
CIRCUIT BREAKER)
NEUTRAL
HOT
FAN 1
FAN 3
N IN
N OUT 1
FAN 4
FAN 2
LINE
120VAC 60 Hz
8A MAX
2A MAX/CKT
1 FEED
4 FAN
CLX-1FAN4
If you require a UL Listed panel, Crestron offers this
service through its UL Listed panel shop. This
includes complete in factory system configuration
and assembly by Crestron for an additional fee.
Terminal Block Installation and Field
Wiring
1. Use the two supplied self-tapping pan Phillips
screws (8B x ¼ length) to secure the terminal
block and the appropriate (left or right) wiring
label to the Crestron Automation Enclosure. The
wiring label lies beneath the terminal block as
shown in the two wiring diagrams on this page.
NOTE:
Both left and right wiring labels are
provided. The left-side labels are common for both
single and double-wide enclosures. The right-side
labels are only used in double-wide enclosures since
the modules and terminal blocks along the right side
must be inverted when mounting.
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Right Side Double-wide Enclosures)
NEUTRAL
(FROM 15
OR 20 AMP
CIRCUIT
BREAKER)
TERMINAL
BLOCK
AREA FOR
MODULE
LOCATION
LABEL
RIGHT SIDE
WIRING LABEL
CRESTRON
TO
LOAD(S)
GROUNDING
TERMINAL
BLOCK
HOT
120VAC 60 Hz
8A MAX
2A MAX/CKT
GND
1 FEED
CLX-1FAN4
4 FAN
N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN
FAN 4
FAN 3
FAN 2
FAN 1
LINE
NOTE:
Use copper conductors only – rated 75
°
C
2. With the circuit breaker turned off, connect the
circuit feed (HOT and NEUTRAL) and
controlled circuit (LOAD) wires to the terminal
block per the markings provided on the wiring
label (as shown in the two wiring diagrams on
this page). Terminal blocks accept one 14 - 10
AWG wire. Wires should be stripped to ½ inch.
Tighten terminal blocks to 9 in-lbs. Do not over
tighten.
NOTE:
Only one fan may be wired per circuit.
3. Grounding terminal blocks are available in the
cabinet for termination of ground wires. Tighten
to 35 in-lbs. (14 – 10 AWG), 40 in-lbs.
(8 AWG), or 45 in-lbs. (6 – 4 AWG).
2
•
Terminal Block & Module: CLT- & CLX-1FAN4
Installation Guide – DOC. 6032A