Crestron Cameo CLW-DIMUEX-P Quick Start Manual Download Page 9

Master and Slave Operation

The CLW-DIMUEX-P supports multipoint dimming when used in
conjunction with a CLW-SLVU-P slave dimmer. Multipoint dimming is
similar to conventional 3- or 4-way switching, allowing dimming control of
a single load from multiple locations in the room.

For more information on master and slave operation, refer to the

CLW-SLVU-P Installation Guide

(Doc. 7364).

Changing the Dim Mode

By default, the device is set to Auto Phase Dimming mode, which allows
the device to automatically toggle between forward and reverse phase
dimming based on the connected load. The device can be set to Auto
Phase Dimming mode or Forward Phase Dimming mode manually.

To set the dimming mode:

1. Open the air-gap switch as described in

Master and Slave Operation

.

2. While power is off, set the dimming mode:

l

Auto Phase Dimming Mode: Press and hold the top button cap.

l

Forward Phase Dimming Mode: Press and hold the bottom button
cap.

3. While holding the appropriate button, close the air-gap to restore

power to the connected load, the device buttons, and the LEDs.

4. After all LEDs have flashed once, release the button cap.

NOTE:

If the dimming mode is set in the control system program, the

LEDs will flash five times and the new mode will not be set. To modify
the parameter, change the setting in the control system program to
"Local Settings" and retry the operation.

5. After the released button's LED flashes once, the device will boot-up in

the selected dimming mode.

Wireless Communications

The device connects to the Crestron network via the infiNET EX
communications protocol. Use the procedures outlined below to join or
leave an infiNET EX network and to verify communications between the
device and the control system.

Joining an infiNET EX Network

Before a device can be used in a lighting system, it must first join an
infiNET EX network by being acquired by an infiNET EX gateway. The
CLW-DIMUEX-P is compatible with the CEN-GWEXER wireless gateway
and the MC4-R media room controller.

NOTE:

A device can be acquired by only one gateway.

1. Put the infiNET EX gateway into Acquire mode from the unit itself or

from Crestron Toolbox™ software, as described in either the

CEN-

GWEXER and CEN-GWEXER-PWE Quick Start

(Doc. 7723) or the

MC4-R and MC4-R-I Quick Start

(Doc. 8545).

NOTE:

In an environment where multiple gateways are installed, only

one gateway should be in Acquire mode at any time.

9

CLW-DIMUEX-P

Quick Start

Cameo® In-Wall Universal Phase Dimmer, 120 VAC

Summary of Contents for Cameo CLW-DIMUEX-P

Page 1: ...load CAUTION TO REDUCE THE RISK OF OVERHEATING AND POSSIBLE DAMAGE TO OTHER EQUIPMENT DO NOT INSTALL TO CONTROL A RECEPTACLE A MOTOR OPERATED APPLIANCE A FLUORESCENT LIGHTING FIXTURE OR A TRANSFORMER...

Page 2: ...ary windings to prevent transformer failure due to overcurrent Installation Install the CLW DIMUEX P 1 Turn power off at the circuit breaker 2 Wire the device as shown in the following diagrams NOTES...

Page 3: ...ower to the transformer If you do not know the input power requirement of the transformer use the bulb s wattage rating to determine proper rating Derating Information for CLW DIMUEX P Dimmers Changin...

Page 4: ...n the left side 4 Attach the button assembly to the device Ensure that the LED strip is on the left side Power to the load the buttons and the LEDs is restored when the button assembly is attached NOT...

Page 5: ...unctions for details Operation NOTES l Before using the CLW DIMUEX P ensure the device is using the latest firmware Check for the latest firmware for the CLW DIMUEX P at www crestron com firmware l Th...

Page 6: ...talled button configuration The device has default preset levels To set new preset levels 1 Adjust the light level to the desired level 2 Tap the program button to enter Programming mode as shown belo...

Page 7: ...te the default functions available for each physical button configuration and tap or hold actuation sequence Single Button Press Double Button Press Press twice within 1 2 second 7 CLW DIMUEX P Quick...

Page 8: ...Single Button Press and Hold Hold for more than 1 2 second 8 CLW DIMUEX P Quick Start Cameo In Wall Universal Phase Dimmer 120 VAC...

Page 9: ...e dimming mode is set in the control system program the LEDs will flash five times and the new mode will not be set To modify the parameter change the setting in the control system program to Local Se...

Page 10: ...tap tap press hold for up to 2 seconds The top button s LED flashes to indicate the communications status Refer to the following table for details LED Communications Status Turns on for 5 seconds The...

Page 11: ...circuit breaker is closed The load is not operational e g lamps are burned out Verify that the load is operational and that the air gap switch is closed The dimmer is in Remote mode Check the SIMPL pr...

Page 12: ...e_license_agreement The product warranty can be found at www crestron com warranty The specific patents that cover Crestron products are listed at www crestron com legal patents Certain Crestron produ...

Reviews: