Troubleshooting
(continued)
Service Manual
51
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Outlet Sensor
Differential
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The readings from the two outlet temperature
sensors are too far apart.
• Check all connections between the outlet temperature
sensors and the control board. Make sure all
connections are dry and secure.
• Check the resistance of the two outlet sensors (see
page 39).
• Replace the control board.
Flue Sensor
Differential
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The readings from the two flue temperature
sensors are too far apart.
• Check all connections between the flue temperature
sensors and the control board. Make sure all
connections are dry and secure.
• Check the resistance of the two flue sensors (see page
39).
• Replace the control board.