Installation
Do not install the detector
Where the temperature is under 0
℃
and over +55
℃
or outdoor
Near to exhaust fan, vaporous, chimney hood, smelly places
Location of the detector should not be very close to apertures and
ventilation channels as air stream may be greater and gas
concentration may decrease.
Location
Natural gas that is comprised of methane gas is lighter than air, in
case of gas leakage; gas rises towards ceiling and accumulates in
areas near ceiling. Therefore, for natural gas, the alarm apparatus
shall be located in a position of 30 cm under the ceiling and 1.5-4
meter(s) away from gas supply. LPG that is comprised of mixture
of propane and butane is heavier than air. In case of gas leakage,
LPG falls down to ground. Therefore, for LPG, the alarm apparatus
shall be located in a position of 30 cm above the floor and 1.5-4
meter(s) away from gas supply.