Installation Instructions: Wall-Mount Dewpoint Probe

technical bulletin

Power and Input Wiring

To wire the Dewpoint Probe to a MultiFlex or 16AI input point, use Belden #8771 three-conduc-
tor shielded 22AWG wire (or equivalent). 

Figure 5

 shows the connection point on the Dewpoint 

Probe’s circuit board and where to connect the wires to the probe as well as the input point. The 
sensor is powered by one of the +12VDC power supply terminals on the MultiFlex or 16AI input 
boards. 

Terminal 1 of the Dewpoint Probe must be connected to a solid earth ground. Also, the input type 
dip switch on the MultiFlex or 16AI input board must be set to the DOWN position. Input type 
dip switches for points #1 through #8 are located on switch bank S1, while points #9 through #16 
are located on switch bank S2. 

E2 Input Setup

NOTE: Do 

NOT

 set up this probe with a sensor type of 

“Dewpoint”; this setting only works for old-style CPC 
Dewpoint Probes (P/N 203-1902). This probe must be set 
up with a sensor type of “Linear.”

1. Log into the E2 and press 

I

 (Input Sum-

mary).

2. Highlight the input point the Dewpoint Probe is con-

nected to, and press 

A

 (Setup).

3. When prompted to select the data type, press 

 

(Analog).

4. In the Analog Input setup screen, enter the following 

information in the fields listed below:

Name

: A description of the sensor’s function 

and/or location (e.g. INDOOR DEWPT).

Sensor Type

: Linear

Eng. Unit

: DF

Low Eng Units

: 0.0

High Eng Units

: 100

5. Press 

J

 to save changes and exit the Analog Input setup screen.

Figure 5 - Dewpoint Probe Wiring

1   2    3   4   5

CIRCUIT BOARD, FRONT VIEW

 (COVER REMOVED)

CABLE

(BELDEN #8771)

RUN CABLE 

THROUGH

WALL OR 

CONDUIT

AND FEED 

END  THROUGH 

HOLE IN

MOUNTING PLATE

1   2    3   4   5

1   2    3   4   5

SH

IELD

 (G

N

D

)

BLACK (SGND)

W

H

ITE (SIG

)

RED (

1

2

V

DC)

CONNECT

TERMINAL 1

TO EARTH 

GROUND

CABLE
(BELDEN #8771)