TECHNICAL BULLETIN

Part #: 026-4807  Revision 0  Date: 02/26/2003

COMPUTER PROCESS CONTROLS - http://www.cpcus.com/

Page 1

Duct-Mounted Humidity Sensor (P/N 203-5771)       

Installation Instructions

CPC specs a duct-mounted relative humidity (RH) sensor with a 0-5VDC output for use in build-
ing control and anti-sweat control applications using CPC input boards.

Specifications

Choosing a Mounting Location

Select a supply air duct that draws air from the area in which you wish to measure relative humid-
ity. You may mount the sensor in any orientation provided the sensor element is in the air stream. 

Mounting

1.

Cut a small circular hole in the duct large 
enough for the sensor tube to fit through.

2.

Bolt the sensor enclosure against the outside of 
the duct wall so that the sensor element fits 
through the hole and into the duct. The enclo-
sure may be mounted horizontally (as shown in 

Figure 1

) or vertically. The screws should be 

tight enough for the foam gasket around the 
bottom of the sensor to form an airtight seal 
between the hole in the duct wall and the out-
side air.

Sensing Element

Digitally profiled thin-film capacitive

Analog Output

0-5VDC; 3-wire, observe polarity

Accuracy

±2% RH over the range 20%-90% RH

Scaling

0-100% RH

Stability

±1%@ 20°C (68°F) annually for 2 years

Input Power

12VDC

Operating 
Humidity Range

0-100% RH

EMC 
Conformance

EN 50081-1, EN 50082-1, EN 61000-4-4, 
EN 61000-4-5, EN 61000-4-3, ENV 
50204, EN 61000-4-6

Temperature 
Coefficient

±0.03% RH /°C over 0-60°C (32-140°F)

Figure 1 - Humidity Sensor - Exploded View