TECHNICAL BULLETIN

Part #: 026-4808  Revision 0  Date: 02/26/2003

COMPUTER PROCESS CONTROLS - http://www.cpcus.com/

Page 1

Outdoor Humidity Sensor (P/N 203-5761) 

Installation Instructions

CPC specs a outdoor relative humidity (RH) sensor with a 0-5VDC output for use in building 
control and anti-sweat control applications using CPC input boards.

Specifications

Choosing a Mounting Location

The outdoor RH sensor should always be mounted on the north side of the building if in the 
Northern Hemisphere, or on the south side if in the Southern Hemisphere. The sensor should be 
mounted under an overhang or otherwise out of direct sunlight (if possible). 

Mounting

1.

Secure the rear side of the enclosure to the outside wall 
using the two mounting brackets, as shown in 

Figure 1

The tube holding the sensor element should point straight 
down.

2.

If you will be running the sensor cable through the wall 
behind the sensor, cut or drill a hole in the wall through 
the hole in the enclosure.

Sensing Element

Digitally profiled thin-film capacitive

Temperature 
Coefficient

±0.03% RH /°C over 0-60°C (32-140°F)

Accuracy

±2% RH over the range 20%-90% RH

Analog Output

0-5VDC; 3-wire, observe polarity

Stability

±1%@ 20°C (68°F) annually for 2 years

Scaling

0-100% RH

Operating 
Humidity Range

0-100% RH

Input Power

12VDC

Figure 1 - Humidity Sensor - Exploded View