MR Series 600K
User Manual
11
Battery power supply mode
When mains abnormal, system will switch to battery input, the Boost circuit promotes the battery
voltage to a certain value and then supply the DC power to the inverter, that makes the AC output
without interruption phenomenon and then protect the load. The specific work process is as follows.
When mains abnormal at any time, the rectifier will switch to battery input immediately to maintain
the voltage of DC electrolysis, which guarantee the inverter without power down. Before battery
discharge completely, if mains recovers, the rectifier will switch to mains input and charge battery at
the same time. During the switch between grid power supply and battery power supply, the inverter
output cannot power down.
In battery power supply mode, if mains does not recover normal all the time, and the battery energy is
running out, the UPS will send sound & light alarm, and stop working at the max. discharge point, and
long beeps to alarm. At that time, the load will power down.
Bypass power supply mode
When system abnormal (such as over-temperature, short-circuit, output voltage abnormal or overload)
and exceed the bear range, the inverter will shut down to avoid damage automatically. If mains still
normal at this time, it will turn to bypass to supply power for load. The specific work process is as
follows.
If the inverter circuit fault or inverter overload and exceed the bear range, the UPS will turn to bypass
to output. During bypass power supply, if fault or overload removed, the UPS will start inverter and
begin to supply power for load. When the load is serious overload and exceeds the bypass bear range,
the UPS will close the bypass output, and it will cause user load power down. When load fault or short
circuit, the UPS will switch to bypass to supply power from inverter. If the short-circuit is serious, the
UPS mains breaker and bypass breaker may trip out. After suffering the short-circuit fault, UPS will try
to restart. If the short-circuit is removed, the UPS will switch to inverter; if the fault is not removed,
the UPS will try to restart for 5 times. 5 times later, the UPS will turn to fault protection. At this time, it
needs to power off or press the touch screen to shut down the UPS, and restart the UPS, and then, it
will recover normal work.
Maintenance bypass power supply mode
When the UPS needs to be maintained and the power supply for load cannot be interrupted, user can
shut down the inverter and make the UPS works in bypass status, then switch on the maintenance
bypass breaker and switch off the mains pint breaker and bypass power supply breaker. During the
Summary of Contents for MR Series
Page 1: ...Uninterruptible power supply COVER MR 600 kVA User manual ...
Page 2: ......
Page 10: ......
Page 36: ......
Page 38: ...MR Series 600K User Manual 28 3 2 Installation Preparation 3 2 1 Installation Tools Tools ...
Page 56: ......
Page 60: ...MR Series 600K User Manual 58 Figure4 4 Fault protection with no output Figure4 5 Shutdown ...
Page 61: ...MR Series 600K User Manual 59 Figure4 6 Exit parallel system Figure4 7 Bypass output ...
Page 62: ...MR Series 600K User Manual 60 Figure4 8 Battery INV output Figure4 9 Mains INV output ...
Page 89: ...MR Series 600K User Manual 87 Figure4 57 Confirm to power off ...