7
EN
2-5. SR-1600 Plus De-rating Curve
Figure 3. SR-1600 Plus de-rating curve: SR-1600
Plus-124/224
Figure 4. SR-1600 Plus de-rating curve: SR-1600 Plus-148/248
2-6. Protection Mechanism
Type
Over Voltage
Under Voltage
Shutdown
Restart
Alarm
Shutdown
Restart
Alarm
110 Vac
130
±
3%
125
±
3%
125
±
3%
90
±
3%
95
±
3%
95
±
3%
230 Vac
260
±
3%
250
±
3%
250
±
3%
180
±
3%
190
±
3%
190
±
3%
24 Vdc
34
±
0.5
28
±
0.5
33
±
0.5
18
±
0.5
25
±
0.5
21
±
0.5
48 Vdc
68
±
1
56
±
1
66
±
1
36
±
1
50
±
1
42
±
1
Table 2. SR-1600 Plus protection mechanism