2
G 521 - RFG 361
C1 Eng.
25.11.08 MZ
Rev. 02
We reserve the right to make changes without notice
COSTER
5. TECHNICAL DATA
Power supply
230 V ~ ± 10 %
Frequency
50…60 Hz
Consumption
3 VA
Protection
IP40
Radiodio sturbances
VDE0875/0871
Vibration test
with 2g (DIN 40046)
Output relay:
– switch
voltage free
– maximum switched voltage
250 V ~
– maximum switched current
5 (1) A
Construction standards
CEI
Enclosure
DIN 3E module
Installation
on DIN 35 rail
Materials:
– base
Nylon
– cover
ABS
Ambient temperature:
– operating
0…45°C
– storage
– 25…+ 60°C
Ambient humidity
Class F DIN 40040
Weight
0.250 kg
Pre-alarm & alarm intervention thresholds
(in bold type threshold with Sensitivity = 0)
Methane
– Alarm methane
0.5…
0.8
…1.25 %
5,000…
8,000
…12,500 ppm
– Pre-alarm methane
0.3…
0.5
…0.8 %
3,000…
5,000
…8,000 ppM
Propane-LPG
– Alarm-Propane-LPG
0.22…
0.35
…0.56 %
2,200…
3,500
…5,600 ppm
– Pre-alarm propane-LPG
0.14…
0.22
…0.35 %
1,400…
2,200
…3,500 ppM
Carbon monoxide (CO)
Warning: in detecting carbon monoxide (CO), the levels and
intervention times are processed and controlled by
a microprocessor. The “Sensitivity” control must
obviously be set in the “0” position.
– Carbon monoxide:
“thr time”
< 50 ppm: no alarm
50...100 ppm: 60 minutes
100...300 ppm: 10 minutes
> 300 ppm: immediate alarm
–Carbon monoxide (CO) pre-alarm:
time between
exceeding alarm threshold and alarm
3. OVERALL DIMENSIONS
1 – Protective cover for electronic components
2 – Base with transformer, relay and terminal blocks
3 – Screws for securing base and cover
4 – DIN rail securing elements
5 – DIN rail release lever
1
2
3
4
5
4. FACIA
1 – Sensitivity control knob
2 – Power LED
3 – Sensor fault or wrong connection LED
4 – Pre-alarm (flashing LED) or alarm (LED stays lit)
5 – Reset button
4
3
2
1
5
53
50.5
21