12
A 511 - DTC 628 Eng.
06.12.05 LB
We reserve the right to make changes without notice
16.
4
Holidays periods
Each holiday period, defined by the start and end dates, sets an operating program, the same for all
holiday periods, which replaces that in use.
At the end of each period the controller returns to the previous program.
• Number of holiday periods you wish to use (1…25).
Choose the program to be used during all the holiday periods;
– 7 DAY 1-2
= with one of the 2 7day program (
M2.
9…15
) ;
– 24 HOUR 1-7
= with one of the 7 24hour program (
M2.
2…7
) ;
– NORMAL 1…5 xx.x c = with one of the 5 Compens. normal room temp. (
M1.
1…5
) ;
– SETBACK 1-2 xx.x c = with one of the 2 Compens. setback room temp. (
M1.
6-7
) ;
– FROSTPROT xx.x c = with the Compensated Frostprot room temp. (
M1.
8
) ;
– FIXED P 1-2
xx c = with one of 2 boiler temp. Fixed Point (
M1.
9-10
) ;
– OFF
= always Off.
Enter the data for each single period:
• Hol xx : number period (1…25) ; • Start : XX : sets start time of period :
– NO = period not used;
– 00 = start at 00 hours
– 12 = start at 12 hours
• Fr : xx.xx to : xx.xx : day and month of start and end of holiday period,
For a period of a single day set the same date for start and end.
To cancel dates of holiday period keep + and – keys pressed at the same time.
16.
5
Special period
Period in which an operating progtamme is set to meet special requirements and which temporarily
replaces the programme set in
M0.
2
:
• Special programme :
– 7 DAY 1-2
= with one of the 2 7day programmes (
M2.
9…15
) ;
– 24 HOUR 1-7
= with one of the 7 24hour programmes(
M2.
2…7
) ;
– NORMAL 1…5 xx.x c = with one of the 5 Compens. normal room temp. (
M1.
1…5
) ;
– SETBACK 1-2 xx.x c = with one of the 2 Compens. setback room temp. (
M1.
6-7
) ;
– FROSTPROT xx.x c = with the Compensated Frostprot room temp. (
M1.
8
) ;
– FIXED P 1-2
xx c = with one of 2 boiler temp. Fixed Point (
M1.
9-10
) ;
– OFF
= always Off.
• Fr - - . - - t o - - . - - = day and month of start and end of special period.
To cancel the dates of the special period keep + and – keys pressed at the same time.
16.
6
Heating season period
Sets the winter season heating period.
• Heating season
Fr - - . - - to - - . - - = day and month of start and end of heating season.
In summer period the boiler remains OFF. Only the remote control (A) can switch the boiler on
again.
To cancel the period keep p and – keys at the same time.
16.
7
British Summer Time (BST)
The controller automatically changes the current time according to the BST period.
• Fr - - . - - to - - . - - = day and month of start and end of BST period,
To cancel the period keep p and – keys at the same time.
M2.
17
H o l i d a y p r o g r a m
F R O S P R O T 6 . 0 c
M0.
5
S p e c i a l p r o g r a m
2 4 H O U R 1
M0.
6
S p e c i a l p e r i o d
F r : - - . - - t o : - - . - -
M2.
19
H e a t i n g s e a s o n
F r : - - . - - t o : - - . - -
M2.
20
S u m me r t i m e ( B S T )
F r : 2 9 . 0 3 t o : 2 6 . 1 0
M2.
16
H o w m a n y h o l i d a y
p e r i o d s ? 0
M2.
18
H o l 0 1 S t a r t N O
F r : - - . - - t o : - - . - -