background image

Instruction Manual: COSTAR® 12SIR, 12V System CO Alarm 

QGI P/N 099-0066-01 REV 10/26/01 

Page 5 of 7 

Figure 6 

 

A.) 

Parallel with the hallway walls when ceiling mounting 

 

B.) 

Pointed upward when wall mounting 

9.4 

 Attach the mounting plate on the wall.  Be sure the UP text and arrow are facing up.  Use the screws and anchors provided 

to secure the mounting plate. 
9.5 WIRING 

INSTALLATION 

 

Internal terminal block for 14-22 AWG wires.  8 screw terminals at 0.2" (5 mm) spacing. 

9.5.1 

Drill hole in wall or ceiling at center of plate, and pull system wires through the hole. 

9.5.2 

Remove alarm cover by using the special tool provided on the three locking tabs on the alarm base.  (see figure 4) 

 

 

 

Figure 4 

 

9.5.2 

Pull wires through hole at center of alarm base and connect to the internal terminal block as shown on the following wiring 
diagrams.  (see figure 5) 

 

 

 Figure 5

 

 
NOTE:  The form 'C' relay contacts may be wired either N.O. or N.C. according to system panel requirements.  These alarms are not 
designed to drive auxiliary devices 
 
9.5.4 

The 12SIR alarms do not include power supervision.  This may be accomplished by installing a power supervision relay at 

the end of the alarm power circuit.  No internal backup battery. 
9.6 

Alignment marks are provided on the edge of the trim plate and the alarm.  After 

installing the mounting plate, place the alarm on the mounting plate with the alignment marks 
lined up. Twist the alarm in the direction indicated by the "ON" arrow on the alarm cover 
until it locks in place. 
9.7 

To make your carbon monoxide alarm tamper resistant, a locking pin has been 

provided in the bag with the screws and anchors.  Using this pin will deter children and others 
from removing the alarm from the mounting plate.  To use the pin insert it into the hole in the 
side of the alarm after the alarm has been installed on the mounting plate (see figure 6).  To 
remove the alarm, use long nose pliers pull the pin out of the hole; it is now possible to 
remove the alarm from the mounting plate. 

 Test alarm immediately following installation

 and weekly for proper operation by 

pushing the test button until a short beep is heard (approximately three seconds).  Release the button.  The alarm will then test itself 

Summary of Contents for 12SIR

Page 1: ...thier indoor air quality for us all To your good health and safety Mark Goldstein Ph D President Quantum Group Inc 1 0 GENERAL DESCRIPTION This CO alarm is suited for residences motels hotels and commercial or industrial system applications The 12SIR is designed for 4 6 wire connection to 12VDC alarm system control panels Reference UL Listed Household Fire and or Burglary Panel with auxiliary sign...

Page 2: ...edical problems may consider using warning devices that provide audible and visual signals for carbon monoxide concentrations under 30 ppm 5 0 WHAT YOU SHOULD DO IF THE ALARM SOUNDS WARNING Activation of this device indicates the presence of carbon monoxide CO which can KILL YOU If alarm sounds 5 1 1 Operate reset silence button 5 2 2 Call your emergency services ________ __________ fire departmen...

Page 3: ...poisonous CO conditions at a reasonable cost This alarm monitors the air and when it senses CO it activates its built in alarm It can provide precious time for you and your family to escape from your residence before CO can seriously injure or kill However such an early warning is possible only if the alarm is located installed and maintained as specified in the Owner s Manual 7 0 IMPORTANT WHAT Y...

Page 4: ...o 37 8 C 40 F to 100 F Good ventilation is recommended when household cleaning supplies or similar contaminants are stored or frequently used 8 7 CONDITIONS WHICH CAN RESULT IN TEMPORARY CO SITUATIONS 8 7 1 Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions such as i Wind direction and or velocity including high gusts of wind Heavy air in the vent...

Page 5: ...ary devices 9 5 4 The 12SIR alarms do not include power supervision This may be accomplished by installing a power supervision relay at the end of the alarm power circuit No internal backup battery 9 6 Alignment marks are provided on the edge of the trim plate and the alarm After installing the mounting plate place the alarm on the mounting plate with the alignment marks lined up Twist the alarm i...

Page 6: ... requires immediate servicing 10 3 1 Trouble RELAY output 1 form C dry contacts non latching current capacity is 100 microAmp 0 1A Trouble relay connection to panel is optional 11 0 MAINTENANCE CLEANING YOUR ALARM 11 1 Keep your CO alarms clean do not wash 11 2 To clean your alarm remove it from the mounting bracket as outlined in section 9 2 11 3 You can clean the interior of your alarm by using ...

Page 7: ...R THAN THAT OF THIS WRITTEN WARRANTY EXCEPT AS REQUIRED BY LAW INCLUDING BUT NOT LIMITED TO ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR AGAINST INFRINGEMENT OR ANY EXPRESS OR IMPLIED WARRANTY ARISING OUT OF TRADE USAGE OR OUT OF A COURSE OF DEALING OR COURSE OF PERFORMANCE Quantum Group Inc has not authorized any other party to extend any other warranties in connection w...