Costar 12-24SIR Owner'S Manual Download Page 2

77..00 IIM

MPPOORRTTAANNTT:: W

WHHAATT YYOOUURR CCOO AALLAARRM

M CCAANN AANNDD CCAANNNNOOTT DDOO

If bedroom doors are usually closed at night, alarms should be

placed in each bedroom as well as in the common hallway between
them. CO alarms may not sense CO on a different level of a resi-
dence or building. For example, a second floor alarm may not sense
a CO leak on the first floor or in the basement.

Therefore, alarms should be placed on every level of a residence

or building. If the alarm is located outside of a bedroom, it may not
wake up a sound sleeper, especially if the bedroom door is closed or
only partly open. If the alarm is located on a different level of the resi-
dence than the bedrooms, it is even less likely to wake up people
sleeping in the bedroom.  Installing CO alarms may qualify you for
lower homeowner’s insurance rates, but CO alarms are not a substi-
tute for insurance. Homeowners and renters should continue to
insure their lives and property.

WARNING:

The COSTAR® Model 12-24SIR CO Alarm 

is not

designed for marine, RV, or aeronautical use.  

NOTE:

This unit contains no batteries and will not operate without

power.

88..00 IINNSSTTAALLLLIINNGG TTHHEE CCOOSSTTAARR®

® 1122--2244SSIIRR FFOORR RREESSIIDDEENNTTIIAALL UUSSEE 

8.1 RECOMMENDATIONS

One of the most important considerations in any CO alarm system

is the location of the alarms.  Statistics of the National Fire Protection
Association (NFPA) show that most of the fatal CO occurrences hap-
pen at night while people are sleeping. Early warning of CO is best
achieved by the correct installation of CO alarms. Placement of an
alarm in a garage may cause an alarm due to CO from automotive
exhaust.
8.2 RECOMMENDED MOUNTING LOCATIONS 

Put a CO alarm inside each bedroom where the occupant closes

the door while sleeping.  A closed door can block particulate smoke,
but CO gas is likely to get through.

Figure 1:

Recommended CO

alarm placement for single floor

residence.

Figure 2:

Recommended CO

alarm placement for multi-

level residence.

8.3 This CO alarm must be mounted on the wall or ceiling.

8.4 WALL LOCATION: Locate top of the alarm 5 - 6 feet from the

floor.

Figure 3:

Recommended CO alarm mounting location is 5 to 6

feet from floor.

8.5 CEILING LOCATION: 

Alarm should be mounted as close as possible to the center of a

hallway or room.  If this is not possible, the edge of the alarm should
be at least 4 inches from any wall.
8.6 LOCATIONS TO AVOID

Placing units where they will not operate properly causes nui-

sance alarms.To avoid nuisance alarms, do not place units:

– Within 5 feet (1.5m) of any cooking appliance or furnace.
– Near an open window or door, because the fresh air entering
the opening may delay CO from reaching the alarm.
– In damp or very humid areas or next to bathrooms with show-
ers. Install detectors at least 10 feet (3 meters) away from bath-
rooms.
– In very cold or very hot environments or in unheated buildings or
outdoor rooms where the temperature can go below or above the
operating range of the alarm.  Temperature limits for proper opera-
tion are 4.4° C to 37.8° C (40° F to 100° F).
– Good ventilation is recommended when household cleaning
supplies or similar contaminants are stored or frequently used.

8.7  CONDITIONS WHICH CAN RESULT IN TEMPORARY CO SIT-

UATIONS:

8.7.1Excessive spillage or reverse venting of fuel burning appliances

caused by outdoor ambient conditions, such as:

i) Wind direction and/or velocity, including high gusts of wind.
Heavy air in the vent pipes (cold/humid air with extended periods
between cycles).
ii) Negative pressure differential resulting from the use of exhaust
fans.
iii) Simultaneous operation of several fuel burning appliances
competing for limited internal air.
iv) Vent pipe connections vibrating loose from clothes dryers, fur-
naces, or water heaters.
v) Obstructions in or unconventional vent pipe designs which can
amplify the above situations.

8.7.2Extended operation of unvented fuel burning devices (range,

oven, fireplace, etc.)

8.7.3Temperature inversions, which can trap exhaust gasses near

the ground.

8.7.4Car idling in an open or closed area garage, or near a home.

99..00 IINNSSTTAALLLLAATTIIOONN IINNSSTTRRUUCCTTIIOONNSS::  CCAAUUTTIIOONN!!!! RREEAADD CCAARREEFFUULLLLYY

9.1 Select proper location
9.2 A mounting plate is provided on the back of the alarm.  Remove

the mounting plate from the back of the alarm by holding the
mounting plate and twisting the alarm in the direction indicated by
the “OFF” arrow on the alarm cover.

9.3 To insure aesthetic alignment of the alarm with the hallway or

wall, the UP ARROW on the mounting plate must be :

A.) Parallel with the hallway walls when ceiling mounting
B.) Pointed upward when wall mounting

9.4 Attach the mounting plate on the wall.  Be sure the UP text and

arrow are facing up.  Use the screws and anchors provided to
secure the mounting plate.

9.5 WIRING INSTALLATION

Internal terminal block for 14-22 AWG wires.  8 screw terminals at
0.2” (5 mm) spacing.

9.5.1

Drill hole in wall or ceiling at center of plate, and pull system

wires through the hole. 

9.5.2

Remove alarm cover by using the special tool provided on

the three locking tabs on the alarm base.  (see figure 4)

Figure 4

9.5.3

Pull wires through hole at center of alarm base and connect

to the internal terminal block as shown on the following wiring
diagrams.  (see figure 5)

Figure 5

NOTE:The form ‘C’ relay contacts may be wired either N.O. or N.C.

according to system panel requirements.  These alarms are not
designed to drive auxiliary devices

9

.

5.4

The 12-24SIR alarms do not include power supervision.

This may be accomplished by installing a power supervision relay
at the end of the alarm power circuit (see Figure 6 below).  There
is no internal backup battery.

9.6 After installing the mounting plate, place the alarm on the mount-

ing plate. Twist the alarm in the direction indicated by the “ON”
arrow on the alarm cover until it locks in place.

Family Room

Bedroom

Living Room

Kitchen

Dining Room

Bedroom

Bedroom

= Carbon Monoxide alarm location

= Carbon Monoxide alarm
    location for multi-level residence

Bedroom

Bedroom

Bedroom

Garage

Kitchen

Living Room

Basement

= Carbon Monoxide alarm mounting location

Inside wall location

Height 5' - 6' from floor

Summary of Contents for 12-24SIR

Page 1: ...al signals for carbon monoxide concentrations under 30 ppm 5 5 0 0 W WH HA AT T Y YO OU U S SH HO OU UL LD D D DO O I IF F T TH HE E A AL LA AR RM M S SO OU UN ND DS S WARNING Activation of this device indicates the presence of carbon monoxide CO which can KILL YOU If alarm sounds 1 Operate reset silence button 2 Call your emergency services __________________ fire department or 911 3 Immediately ...

Page 2: ...operating range of the alarm Temperature limits for proper opera tion are 4 4 C to 37 8 C 40 F to 100 F Good ventilation is recommended when household cleaning supplies or similar contaminants are stored or frequently used 8 7 CONDITIONS WHICH CAN RESULT IN TEMPORARY CO SIT UATIONS 8 7 1Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions such as i ...

Page 3: ...TROUBLE RELAY COSTAR MODEL 12 24SIR CARBON MONOXIDE ALARM COSTAR MODEL 12 24SIR CARBON MONOXIDE ALARM COSTAR MODEL 12 24SIR CARBON MONOXIDE ALARM POWER 12VDC NC C NO ALARM RELAY NC C NO TROUBLE RELAY END OF LINE rRESISTOR OPTIONAL POWER SUPERVISION RELAY OPTIONAL COIL OPTIONAL OPTIONAL OPTIONAL Figure 6 12 24VDC System Multiple Alarms Installation Wiring Diagram ...

Page 4: ...our 12 24SIR alarm NOTE REGULAR TESTING IS RECOMMENDED 12 0 PERIODIC ALARM TESTING Test the alarm weekly for proper operation by pushing the test button until a short beep is heard approximately three seconds Release the button The alarm will then test itself for proper operation and the RED LED light will flash 4 6 times At completion of the test the alarm will sound 2 pat terns The alarm then re...

Reviews: