Table 4.6 Warranty (LMA240F-24-Y)
Mounting
Method
Cooling
Method
Average ambient
temperature (year)
Warranty
Io
[
75%
75%<Io
[
100%
A
Convection Ta = 50
C
or less
5years
5years
B
Convection
Ta = 35
C
or less
5years
5years
Ta = 45
C
5years
3years
C, D
Convection Ta = 35
C
or less
5years
5years
E
Convection
Ta = 25
C
or less
5years
5years
Ta = 35
C
5years
3years
F
Convection Ta = 30
C
or less
5years
5years
A,B,C,D,E,F Forced air Ta = 60
C
5years
3years
5 Ground
¡
When installing the power supply with your unit, ensure that the
input FG terminal of CN1 or mounting hole FG is connected to
safety ground of the unit.
6 Option and Others
6.1 Outline of options
¿
-C
-
Option -C models have coated internal PCB for better moisture
resistance.
¿
-G
-
Option -G models are low leakage current type.
-
Differences from standard versions are summarized in Table 6.1.
Table 6.1 Low leakage current type
Leakage Current
(AC100V 60Hz)
0.05mA max
Conducted Noise
N/A
Output Ripple Noise
Please contact us for details about
Ripple Noise
*
This is the value that measured on measuring board with capaci-
tor of 22μF at 150mm from output connector.
Measured by 20MHz oscilloscope or Ripple-Noize meter (Equivalent
to KEISOKU-GIKEN:RM-103).
¿
-H
0
t [sec]
t
1
t
2
l
l
O
P
l
ave
: average current
: peak current
Output current [A
]
t
1
[
10 [sec], l
ave
=
I
P
t
1
+I
O
t
2
t
1
+t
2
[
rated current,
t
1
t
1
+t
2
[
0.40 (Refer to below chart)
Duty is depended on peak load, refer to below chart.
1
AC100V
2
AC200V
Duty [%
]
10
0
20
40
Peak Wattage[W]
100
160
200
LMA100F
Duty [%
]
10
0
20
40
Peak Wattage[W]
150
240
300
1
AC100V
2
AC200V
LMA150F
3
Duty [%
]
10
0
5
20
40
Peak Wattage[W]
240
360
480
Forced air
1
AC100V
2
AC200V
LMA240
Fig.6.1 Derating of peak loading
AC-DC Power Supplies Medical Type
Instruction Manual
LMA-15
June 29, 2020