1 Function

1.1  Input voltage range

¡

The range is from 85 VAC to 264 VAC or 120 VDC to 350 VDC.

¡

In cases that conform with safety standard, input voltage range is 

AC100-AC240V(50/60Hz).

¡

AC input voltage must have a range from 85 VAC to 264 VAC for 

normal operation.  If the wrong input is applied,  the unit will not 

operate properly and/or may be damaged.

1.2  Inrush current limiting

¡

Inrush current limiting is built-in.

¡

If a switch is being used for input, ensure that it is confi gured  to 

handle the input inrush current.

¡

A thyristor is used for protection from inrush current. When turning 

the power OFF and then ON again within a short period of time, 

inrush current limiting may be disabled; therefore ensure enough 

time before switching ON. 

1.3  Overcurrent protection

¡

Overcurrent protection is built-in and comes into effect at over 

101%  of the peak current in.  Overcurrent protection prevents the 

unit from short circuit and overcurrent condition.

The unit automatically recovers when the fault condition is cleared.

¿

Intermittent current characteristics

¡

When the output voltage drops more than 50% of the rated output 

voltage value at overcurrent,  the average output current is re-

duced by intermittent operation of power supply.

1.4  Peakcurrent protection

¡

Peakcurrent protection is built-in (The protection circuit operates 

when load current exceeds the rating current and the use deviates 

from the condition in Instruction Manual 4).

If this function comes into effect,  the output is shut down (delayed 

shut down).

The minimum interval of AC recycling for recovery is 3 to 4 min-

utes (

*

).

*

The recovery time varies depending on the voltage and load at 

the time the protection activated.

1.5  Thermal protection

¡

Thermal protection circuit is built-in and shut down under following 

condition.

1

When the current and the temperature which exceed from the 

derating curve.

2

The case FAN stops or air fl ow is interrupted and the amount of 

the wind decreases.

If the thermal protection activates, shut off input voltage, remove 

the cause of the overheating, wait for the unit to cool down, and 

recycle to recover output voltage. 

1.6  Overvoltage protection

¡

Overvoltage protection is built in. When the overvoltage protec-

tion activates, shut off input, wait for at least 3 to 4 minutes, and 

recycle to recover output voltage(

*

). 

*

The recovery time varies depending on input voltage.

Remarks : 

Please avoid applying the over-rated voltage to the out-

put terminal.  Power supply may operate incorrectly or fail.  Incase 

of operating a motor etc.  ,  please install an external diode on the 

output terminal to protect the unit.

1.7  Output voltage adjustment range

¡

Adjustment of output voltage is possible by using potentiometer.

¡

Output voltage is increased by turning potentiometer clockwise 

and is decreased by turning potentiometer counterclockwise.

1.8  Isolation

¡

For a receiving inspection,  such as Hi-Pot test gradually increase 

(decrease) the voltage for the start (shut down).

Avoid using Hi-Pot tester with the timer because it may generate 

voltage a few times higher than the applied voltage,  at ON/OFF of 

a timer.

If the unit is tested on the isolation between input & output and 

output & FG, remote ON/OFF (option) must be shorted to outputs.

2 Assembling and

 Installation Method

2.1  Installation method

¡

When two or more power supplies are used side by side,  position 

them with proper intervals to allow enough air ventilation.  Ambi-

ent temperature around each power supply should not exceed the 

temperature range shown in derating curve.

¡

Fix fi rmly,  considering weight,  though it can be used by the instal-

lation method shown in Fig.2.2.

2.2  Mounting screw

¡

The screw should be inserted up to 6mm max from outside of the 

power supply to keep a distance between inside parts and an iso-

lation (Fig.2.1).

AC-DC Power Supplies Enclosed Type

Instruction Manual

ADA-10

ADA

me̲ada1.indd   ADA-10

me ada1 indd ADA-10

2015/08/07   9:23:57

2015/08/07 9:23:57

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for ADA1000F

Page 1: ...ss underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos...

Page 2: ...erter Active filter Active filter Active filter A current Input 130 85 130 85 85 operation availability Series Parallel Parallel operation Yes PCB Pattern SCR Inrush protection current FR 4 Material D...

Page 3: ...ADA 10 ADA 10 ADA 10 ADA 10 2 1 Installation method 2 2 Mounting screw 2 3 Derating 2 4 Expectancy life and warranty 2 5 Current monitor 3 Series Operation and Parallel Operation ADA 12 3 1 Series ope...

Page 4: ...The case FAN stops or air flow is interrupted and the amount of the wind decreases If the thermal protection activates shut off input voltage remove the cause of the overheating wait for the unit to c...

Page 5: ...nvection as shown in Fig 2 2 2Do not block the ventilation hole In case of ADA600F 24 load factor 100 means output 24V 21A at ACIN100V 24V 25A at ACIN200V In case of ADA750F 24 load factor 100 means o...

Page 6: ...minal and V terminal or the operation may be mulfunction Please use an oscilloscope for pulse loads 3 2 Parallel operation master slave operation Parallel operation is available by connecting below As...

Page 7: ...the output voltage fluctuates oc casionally The minimum current is different depend on the model and the number of parallel operation so please consult us at any time In parallel operation output vol...

Page 8: ...r Supplies Enclosed Type Instruction Manual ADA 14 ADA G Fig 5 2 Part around terminal block T Fig 5 3 Option J Fig 5 1 Option F Table 5 1 Low leakage type Between RC and RC SW ON 4 5 12 5V SW OFF 0 0...

Page 9: ...ication is shown Table 5 2 Special harness is prepared refer to option parts Consult us external view in details Each alarm PF LV is isolated from input output and FG AC DC Power Supplies Enclosed Typ...

Page 10: ...with standard model The following electric specifications are different from standard model 5If diodes are used to configure a circuit to achieve even higher reliability use connections as in Fig 5 9...

Page 11: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Reviews: