FS500-EP SERIES
REVISION # 0000
DATE: 04/03/2019
23
Check the following items at the intervals listed:
CHECK LIST
DESCRIPTION
EVERY
3 MONTHS
EVERY
6 MONTHS
EVERY
12 MONTHS
Drive Chain
Check for excessive slack.
Check & adjust as required
Lubricate.
●
Sprockets
Check set screw tightness
●
Fasteners
Check & tighten as required
●
Bearings & Shafts Check for wear & lubricate
●
Drop-test
Inspect door, drop-test for
proper operation and full
closure per NFPA-80
●
Do not lubricate motor. Motor bearings are rated for continuous operation.
Inspect and service whenever a malfunction either door or operator is observed or
suspected.
Before servicing, always disconnect power supply to the operator.
Replace fuses only with those of the same type and rating.
All replacement parts must be obtained from the door manufacturer per NFPA-80.
Do not place hands or tools in or near the operator when the power is
connected or when testing control or sensing devices. Always
disconnect power before servicing or adjusting the operator.
WARNING
Summary of Contents for FS-500EP Series
Page 15: ...14 FS500 EP SERIES REVISION 0000 DATE 04 03 2019 NOTE ...
Page 16: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 15 NOTE ...
Page 17: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 16 ...
Page 18: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 17 ...
Page 19: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 18 ...
Page 20: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 19 ...
Page 28: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 27 APPENDIX 4 1 NO 2 OFF ON PK PK ...