Errors and malfunctions

Cornelius Deutschland GmbH

Document no. TD1002000

Version 01/10/2019, Index 2

Operator manual Undercounter cooler
Energize 2-5 HC
36

Only soda is being 
dispensed

Syrup container is empty

Connect a new syrup container; 
see chapter 4.2

Connections on the syrup contain-
er are not properly connected

Connect the connections on the 
syrup container properly (see doc-
umentation on the syrup contain-
er)

CO

2

 feed pressure for the syrup 

circuit is set incorrectly on the rele-
vant pressure-reducing valve

Adjust the CO

2

 feed pressure to 

the required value (see documen-
tation on the CO

2

 system)

Syrup tube is not connected to the 
syrup container

Connect the syrup tube; see chap-
ter 4.2

Syrup tube is contaminated

Please contact your service part-
ner

Incorrectly set valve on the tower

Please contact your service part-
ner

Defective valve on the tower

Please contact your service part-
ner

Shut-off valve or pressure-reduc-
ing valve for the fresh water supply 
is closed

Open the shut-off valve and pres-
sure-reducing valve for the fresh 
water supply (see documentation 
on the drinking water system)

Water pressure too high or too low Check the water pressure on the 

pressure-reducing valve and ad-
just, if necessary; see chapter 4.1

Only syrup is being 
dispensed

Circulation pump is switched off

Switch on the circulation pump; 
see chapter 4.1

Circulation pump is defective

Please contact your service part-
ner

Carbonator pump is switched off

Switch on the carbonator pump; 
see chapter 4.1

Carbonator pump is defective

Please contact your service part-
ner

Water in the cooling coils is frozen Please contact your service part-

ner

Soda/syrup ratio is 
incorrect

Too little/too much soda

Please contact your service part-
ner

Too little/too much syrup

Please contact your service part-
ner

CO

2

 feed pressure for the syrup 

circuit is set incorrectly on the rele-
vant pressure-reducing valve

Adjust the CO

2

 feed pressure to 

the required value (see documen-
tation on the CO

2

 system)

Fault

Probable cause

Remedy

Summary of Contents for 221001320

Page 1: ...Operator manual Undercounter cooler Energize 2 5 HC...

Page 2: ...elius com Protection notices in accordance with DIN ISO 16016 2017 08 The reproduction distribution and utilisation of this document as well as the communication of its contents is prohibited unless e...

Page 3: ...semblies and components 13 3 1 1 Undercounter cooler Energize 2 HC 13 3 1 2 Undercounter cooler Energize 3 HC 14 3 1 3 Undercounter cooler Energize 3v HC 15 3 1 4 Undercounter cooler Energize 4 HC 16...

Page 4: ...Energize 5 HC dual 26 3 3 8 CO2 working pressures 26 3 3 9 Control and indicator panel 27 4 Operation 28 4 1 Commissioning 28 4 2 Changing product containers 30 4 3 Shutdown 31 5 Maintenance 32 5 1 Ma...

Page 5: ...allation is to be carried out by an expert in compliance with all of the specifications given in the installation and service manual see the document Undercounter cooler installation and service manua...

Page 6: ...ning and maintenance work must not be carried out by children unattended Use by those under the influence of medication alcohol drugs or other substances which impair their physical sensory or mental...

Page 7: ...and be ex pressly charged with its use This document is to be available to staff at all times If this unit is openly accessible and set up so that untrained staff can use it the operator is to provid...

Page 8: ...a high risk2 which results in serious injuries or death if not avoided WARNING marks a danger with a medium risk2 which may result in serious injury or death if not avoided CAUTION marks a danger with...

Page 9: ...anties If work is undertaken on the unit which is not described in this document Cornelius Deutsch land GmbH shall not assume any liability for any resulting hazards and damages The same applies to de...

Page 10: ...e unit after it has been in continuous use over an ex tended period of time will result in a risk of burns Take appropriate safeguard measures such as by wearing heat resis tant protective gloves DANG...

Page 11: ...air and consequently accu mulates at the bottom and may enter lower lying areas e g sewage sys tems At high concentrations this may lead to a lack of oxygen resulting in a risk of suffocation Lower co...

Page 12: ...e any claim 1 Inspect the cardboard box and make a note of any damage however minimal this may seem If the cardboard box is damaged please make a note of the following on the copy of your freight invo...

Page 13: ...le ambient conditions If possible store the unit in its original packaging Unpacked units must be covered with a dustproof cover No condensate must form under the cover ATTENTION Risk of electrostatic...

Page 14: ...water or cleaning agent residue remaining inside the unit This will lead to damage to internal components Before shipment storage or relocation of the unit the unit is to be cleaned and the cleaning...

Page 15: ...er cooler Energize 2 5 HC 13 3 Description 3 1 Assemblies and components 3 1 1 Undercounter cooler Energize 2 HC The unit comprises the following assemblies Fig 1 1 3 2 6 5 4 1 Cover 2 Cooling unit wi...

Page 16: ...ator manual Undercounter cooler Energize 2 5 HC 14 3 1 2 Undercounter cooler Energize 3 HC The unit comprises the following assemblies Fig 2 1 2 6 5 4 3 1 Tube connections 2 Cover 3 Control and indica...

Page 17: ...2 Operator manual Undercounter cooler Energize 2 5 HC 15 3 1 3 Undercounter cooler Energize 3v HC The unit comprises the following assemblies Fig 3 1 2 4 5 3 1 Control and indicator panel 2 Cover 3 C...

Page 18: ...ator manual Undercounter cooler Energize 2 5 HC 16 3 1 4 Undercounter cooler Energize 4 HC The unit comprises the following assemblies Fig 4 1 2 3 4 5 6 1 Tube connections 2 Cover 3 Control and indica...

Page 19: ...2 Operator manual Undercounter cooler Energize 2 5 HC 17 3 1 5 Undercounter cooler Energize 5 HC single The unit comprises the following assemblies Fig 5 1 2 3 4 5 1 Tube connections 2 Cover 3 Contro...

Page 20: ...x 2 Operator manual Undercounter cooler Energize 2 5 HC 18 3 1 6 Undercounter cooler Energize 5 HC dual The unit comprises the following assemblies Fig 6 1 2 3 4 5 1 Tube connections 2 Cover 3 Control...

Page 21: ...illed to the right temperature in the housing Drinking water is also carbonated This means that still water soda and chilled syrup are available at the re frigerator outlets for postmix beverages When...

Page 22: ...ter cooler Energize 2 HC Description Parameter Value Unit Dimensions Height 635 25 mm in Width 620 24 4 mm in Depth 410 16 1 mm in Dispensing capacity At a dispensing rate of 2 drinks of 0 3 li tres a...

Page 23: ...3 5 mm in Depth 470 18 5 mm in Dispensing capacity At a dispensing rate of 2 drinks of 0 3 li tres a minute1 360 at 2 min Unit Ice build up size Weight 18 kg Ice build up capacity 1440 kcal h Power su...

Page 24: ...13 4 mm in Depth 590 23 2 mm in Dispensing capacity At a dispensing rate of 2 drinks of 0 3 li tres a minute1 360 at 2 min Unit Ice build up size Weight 18 kg Ice build up capacity 1440 kcal h Power s...

Page 25: ...4 mm in Depth 515 20 3 mm in Dispensing capacity At a dispensing rate of 2 drinks of 0 3 li tres a minute1 700 at 2 min Unit Ice build up size Weight 30 kg Ice build up capacity 2400 kcal h Power supp...

Page 26: ...tion and service manual document no TD1002100 Description Parameter Value Unit Dimensions Height 810 31 9 mm in Width 1080 42 5 mm in Depth 690 27 2 mm in Dispensing capacity At a dispensing rate of 4...

Page 27: ...angerous voltage warning sign Fig 8 2 Refrigerant warning sign Fig 8 3 Python connection warning sign Fig 8 4 Carbonator type plate Fig 8 5 Unit type plate Fig 8 4 5 3 2 1 Fig 9 1 Dangerous voltage wa...

Page 28: ...consecutive metre Fig 11 1 Dangerous voltage warning sign Fig 11 2 Unit type plate Fig 11 3 Python connection warning sign Fig 11 4 Refrigerant warning sign Fig 11 5 Carbonator type plate Fig 11 1 2 3...

Page 29: ...range CO2 alarm Fig 13 6 LED green power mains Fig 13 1 2 3 4 5 6 LED Status Description Comment Alarm red Off OK No existing error On Not OK see chapter 6 1 Flashing 1 Hz Not OK see chapter 6 1 Flash...

Page 30: ...injury or equipment damage Please always strictly observe all safety measures and information in structions see chapter 1 The unit has been designed for continuous operation Apart from the daily chec...

Page 31: ...max imum If necessary fill up the water bath with tap water 2 Check that the CO2 bottle valve is open see documenta tion on the CO2 system If necessary open the valve on the CO2 bottle 3 Check the pre...

Page 32: ...at needs changing 2 Exchange the empty product container for a full one and remove the protective cap from its connection NOTICE Do not mix up standard and light products as they are conveyed with dif...

Page 33: ...e carried out by an expert see chapter 1 3 3 as the unit has to be cleaned and drained 1 Close the CO2 bottle valve see documentation on the CO2 system 2 Close the CO2 shut off valves see documentatio...

Page 34: ...ons see chapter 1 5 1 Maintenance table NOTICE The following table provides information on recommended maintenance in tervals to be adapted to the relevant installation situation Interval Components A...

Page 35: ...CO2 system If necessary open the CO2 shut off valves 6 Check that the water supply valve is open see documentation on the water supply valve If necessary open the water supply valve 7 Check the press...

Page 36: ...Cleaning the unit 1 Use a vacuum cleaner to clean the supply and exhaust air grilles of dirt 2 Clean the unit with a clean damp cloth and if necessary an approved cleaning agent 3 Dry the unit with a...

Page 37: ...r not running Switch on the compressor see chapter 4 1 Please contact your service part ner Beverage is too warm and the com pressor is running Excessive beverage dispensing Do not exceed the maximum...

Page 38: ...t off valve or pressure reduc ing valve for the fresh water supply is closed Open the shut off valve and pres sure reducing valve for the fresh water supply see documentation on the drinking water sys...

Page 39: ...the un dercounter cooler see chapter 4 3 Alarm red flashes approx 1x per sec ond Time out due to insufficient water pressure fluctuations carbonator pump is blocked Check the water pressure see chapte...

Page 40: ...plicable documents Cornelius Deutschland GmbH Document no TD1002000 Version 01 10 2019 Index 2 Operator manual Undercounter cooler Energize 2 5 HC 38 7 Applicable documents 7 1 Declaration of conformi...

Page 41: ...RI WKH SODFH RI RSHUDWLRQ 1DPH RI WKH SODFH RI RSHUDWLRQ 6WUHHW DGGUHVV KRXVH QR 3RVWFRGH WRZQ 1DPH RI WKH RSHUDWRU 2SHUDWRU FRS 7KH RSHUDWRU KDV EHHQ LQVWUXFWHG LQ WKH XVH RI WKH XQLW DWH 6WDPS DQG...

Page 42: ...nual Undercounter cooler Energize 2 5 HC 40 QVWDOOHU FRS 7KH RSHUDWRU KDV EHHQ LQVWUXFWHG LQ WKH XVH RI WKH XQLW DWH 6WDPS DQG VLJQDWXUH 2SHUDWRU 6WDPS DQG VLJQDWXUH QVWDOOHU RI WKH XQLW 7KH XQLW KDV...

Page 43: ...FWHG RQ WKH IROORZLQJ WRSLFV HQHUDO VHTXHQFH RI RSHUDWLRQV 5HIHUHQFH WR H LVWLQJ GRFXPHQWDWLRQ OHDQLQJ WKH XQLW DVW QDPH ILUVW QDPH 6LJQDWXUH DVW QDPH ILUVW QDPH 6LJQDWXUH DVW QDPH ILUVW QDPH 6LJQDWXU...

Page 44: ...Deutschland GmbH Document no TD1002000 Version 01 10 2019 Index 2 Operator manual Undercounter cooler Energize 2 5 HC 42 5 Date Component alkaline acidic Chemical agent Cleaning agent Carried out by...

Page 45: ...www cornelius emea com Cornelius Deutschland GmbH Carl Leverkus Str 15 40764 Langenfeld Germany Tel 49 0 21 73 79 3 0 Fax 49 0 21 73 77 4 38 E Mail info cornelius com...

Reviews: