CAUTION:  

Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE 

SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLIANCE CIRCUITS, SM, DSM SYNC MODULES, OR 
COOPER WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS 
OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED.  OVERLOADING POWER SOURCES OR EXCEEDING 
FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH 
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

WIRING AND MOUNTING INFORMATION: 

CAUTION:  

The following figure shows the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  If 

these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. 

CAUTION:  

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed 

multiconductor cable is used. 

 

Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Wheelock recommends use of the largest backbox 
option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the 
product from wiring. 

MAXIMUM NUMBER OF CONDUCTORS

AWG#18    AWG#16    AWG#14    AWG#12

4

  4

4

4

SURFACE (INDOOR/OUTDOOR)

MOUNTING TAB 

(SUPPLIED) 

 WPSBB

  #8-18 SCREWS 

 WOOD SCREWS

 

WARNING:  THIS UNIT MUST BE MOUNTED ON A FLAT SURFACE, SO THAT THE SURFACE COVERS THE ENTIRE BACK SURFACE 

OF THE BACKBOX.  WHEN USED IN AN OUTDOOR APPLICATION OR A NEMA 3R APPLICATION, USE WEATHER PROOF RATED 
CONDUIT FITTING ON ALL KNOCKOUTS OF THE BACKBOX. 

 

 

Figure 1:  Wiring Diagram 

 

OR END OF LINE

FROM PRECEDING
APPLIANCE, FACP

TO NEXT SIGNAL

+

-

STROBES

RESISTOR (EOLR)

OR SYNC MODULE

 

 
 

Figure 2: 

 

 

 

• 

All strobes have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge 

(AWG) wires at each screw terminal.  Strip leads 3/8 inches and connect to screw terminals.   

• 

Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as 

shown in Figure 2.  The polarity shown in the wiring diagrams is for the operation of the 
appliances.  The polarity is reversed by the FACP during supervision.

 

Refer to instruction sheets for SM (P83123), DSM (P83177) or Cooper Wheelock power supplies for additional information. 

1. 

The knock-out opening on the backbox is sized for a ½” conduit and matching connector.  Be sure that a proper watertight conduit fitting is used to 
connect the backbox for outdoor/severe environment applications.  Conduit entrances to the backbox should be selected to provide sufficient wiring 
clearance for the installed product.  Do not pass additional wires (used for other than the signaling appliance) through the backbox.  Such additional 
wires could result in insufficient wiring space for the signaling appliance. 

2. 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the 
appliance. 

3. 

Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  
This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

4. 

Connect 4 field wires to the RSSWP terminal block (polarity must be observed). 

5. 

Bend the 4 field wires up 90

°

 at the connection to the terminal block, then carefully push the 4 field wires into the backbox by hand. 

6. 

Carefully press the RSSWP to the backbox, verifying that the RSSWP is in contact with the gasket all the way around.  It should not be resting on the 
lip of the backbox. 

7. 

Screw the RSSWP to the WPSBB using the #8-18 screws supplied. 

P84824 D  

Sheet 2 of 4

 

Reviews: