background image

CLEARING FAILURE CODES:

A battery failure (LED two blink red) can be cleared by

replacing the battery. Disconnecting the battery and AC

power, or performing a full 90 minute discharge, will

reset the error code, however, it will return if the battery

is faulty.

Charge Circuit (LED three blink red) and lamp/LED

failure (LED four blink red) will clear when the unit suc-

cessfully passes a manual or automatic 30 second test.

INDICATORS:

LED Off - No power to unit, emergency mode.

LED Steady Green - Unit is fully charged and is 

 oat

charging the battery to maintain readiness.

LED Green Pulse - Unit is in a 24 hour fast charge of

the battery.

LED Two Blink Red - Battery has failed a capacity test,

or the battery is disconnected. See “Clearing Failure

Codes” above.

LED Three Blink Red - Battery charge circuit has failed.

See “Clearing Failure Codes” above.

LED Four Blink Red - Lamps have burned out, or on 

an EXIT/Combo, 50% or more of the LEDs have failed. 

See “Clearing Failure Codes” above.

LED Steady Yellow - 30 second test or 10 second quick

test (Fast Charge only).

LED Blinking Yellow - 90 minute test

TROUBLE SHOOTING GUIDE

If LED heads or charge indicator LED does not illuminate, 

check the following:

1.

Check AC supply – verify that unit has 24 hour AC

 

supply.

2.

Unit is shorted or battery is not connected.

3.

Battery discharged. Permit unit to charge for 24 hours

 

and then re-test.

4.

If following the above trouble shooting hints does not

 

solve your problem, contact your local 

Cooper Lighting 

Solutions

 representative for assistance

JMP12

JMP11

JMP10

JMP9

JMP8

JMP7

JMP6

JMP5

JMP4

BATT

LAMPS

N

c

TDI

ICSP

277

JMP13

JMP14

LED/SW

D5

C6

C7

C8

C9

CN4

F1

J1

JK

1

LED1

MOV1

MOV2

PR1

Q1

Q5

R7

R10

R1

3

R15

R18

R30

SW1

120

CN5

+

+

WHITE LEAD - TO NEUTRAL

BLACK LEAD - TO 120V

ORANGE LEAD - TO 277V 

CHARGER/DRIVER PCB

BATTERY

LED HEADS

OFF - EMERGENCY

MODE / POWEROFF

2 BLINK RED -

BATTERY FAILURE

STEADY GREEN -

FULL / FLOAT

CHARGE

STEADY BLINK YELLOW

- 90 MINUTE TEST

3 BLINK RED - CHARGE

CIRCUIT FAILURE

4 BLINK RED - LAMP/

LED FAILURE

STEADY YELLOW -

QUICK TEST

STEADY BLINK

GREEN - FAST

CHARGE

SURE-LITES

TIME DELAY 

JUMPER

MAINTENANCE:

None required. Replace the batteries as needed according 

to ambient conditions. Equipment should be tested every 

30 days in accordance with local codes.

NOTE:

 Servicing of any parts should be performed by quali-

fi ed personnel. Only use replacement parts supplied by 

Cooper Lighting Solutions. Use of unauthorized parts may 

void the warranty.

CAUTION:

 This equipment is furnished with a sophisticated 

low voltage battery dropout circuit to protect the battery 

from over discharge after its useful output has been used. 

Allow 24 hours recharge time after installation or power 

failure prior to 90 minute testing.

Summary of Contents for AtLite Sure-Lites SELDWA29SD

Page 1: ...where the emergency light is to be installed 2 Open the emergency light by inserting a flat screw driver in the two slots on the side of the unit then turning to separate housing from the backplate 3 To mount to a junction box Knock out drill out the appropriate mounting pattern and the wire pass hole in the back plate and the back gasket to fit the J box being used 4 To mount to conduit Unscrew the...

Page 2: ...nd Installation test Press and release the test button once during fast charge blinking green to initiate a 10 second quick test The sign will switch to emergency mode for 10 seconds allowing the installer to verify proper installation of the unit and the LED indicator will turn solid yellow 30 Second Test Press and release the test button once during float charge steady green The indica tor LED wi...

Page 3: ...Unit is shorted or battery is not connected 3 Battery discharged Permit unit to charge for 24 hours and then re test 4 If following the above trouble shooting hints does not solve your problem contact your local Cooper Lighting Solutions representative for assistance JMP12 JMP11 JMP10 JMP9 JMP8 JMP7 JMP6 JMP5 JMP4 BATT LAMPS N c TDI ICSP 277 JMP13 JMP14 LED SW D5 C6 C7 C8 C9 CN4 F1 J1 JK1 LED1 MOV...

Page 4: ...s Reserved Printed in USA Cooper Lighting Solutions is a registered trademark All trademarks are property of their respective owners Cooper Lighting Solutions 1121 Highway 74 South Peachtree City GA 30269 P 770 486 4800 www cooperlighting com ...

Reviews: