background image

The audible/visual notification appliances shall be Wheelock Series NS Horn Strobe appliances and Series NH Horn appliances or 

approved equals. The Series NS appliances shall meet and be listed for UL Standard 1971(Emergency Devices for the Hearing-

Impaired for Indoor Fire Protection Service). The Series NH Horn shall be UL Listed under Standard 464 (Fire Protective Signaling). 

The horn strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible 

with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). 
The audible portion of the appliance shall have a minimum of two (2) field selectable settings for dBA levels (90 and 95 dBA) and shall 

have a choice of continuous or temporal (Code 3) audible outputs.
The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall 

incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series NS shall be of low current design. Where wall mount, 

Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 

for 15/30/75/110 candela. Where ceiling mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable 

settings and shall be rated per UL Standard 1971 for 15/30/75/95 candela or 115/177 candela.  The selector switch for selecting the 

candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 

75 candela on-axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with the Wheelock SM, DSM Sync Modules or the Wheelock PS-24-

8MC Power Supplies with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. 

If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flash-

rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation.
The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single-

gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification 

Appliance Trimplate) shall be provided. 
All notification appliances shall be backward compatible.