Cooper Wheelock S8-70/25 Installation Instructions Download Page 2

MOUNTING INFORMATION 

Figure 1: 

 

 

CAUTION: 

The maximum number of field wires (conductors) that can enter the CBB-8 or other listed equivalent backbox shall comply with the National Electrical 

Code (NEC).   If this limit is exceeded, there may be insufficient space in the backbox to accommodate the field wires.  Stresses from the wires could damage the 
product.   

 

Cooper Wheelock also recommends the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum 
stress on the product from wiring. 

 

The S8-70/25, S8-24MCC and S8-24MCCH models are designed to mount flush in a hung tile ceiling.  The CBB-8 or other listed equivalent backbox is required per 
UL Standard 1480 Speakers for Fire Protective Signaling Systems.  When the speaker and backbox cannot be installed directly through a ceiling tile, a support bridge 
must be used.  Refer to P84239 and P81490 for additional mounting information. 

 

WIRING INFORMATION: 

 

Figure 2: 

Figure 3: 

+ STROBE - COM+

(OPTIONAL)

FROM PRECEDING SPEAKER 

OR FIRE ALARM 

CONTROL PANEL (FACP) 

FROM PRECEDING STROBE 

APPLIANCE OR SYNC MODULE 

 TO NEXT APPLIANCE

 OR EOLR

 TO NEXT SPEAKER

 OR END OF LINE RESISTOR

 (EOLR)

* Refer to Sync Module instruction sheets SM (P83123), DSM (P83177) or 
Wheelock power supplies for additional information. 

 

 

1.  The Low Profile Speaker Strobe model has in-out wiring terminals 

that accept  two #12 to #18 American Wire Gauge (AWG) wires at 
each screw terminal.  Strip leads 3/8 inches and connect to screw 
terminals.  

2.  Break all in-out wire runs on supervised circuits to assure integrity 

of circuit supervision as shown in Figure 3.  The polarity shown in 
the wiring diagrams is for operation of the appliances.  

3.  Connect speaker wires to common and positive of terminal block 

and select the power tap terminal for 1/8W, 1/4W, 1/2W, 1W, 2W, 
4W or 8W; 25V or 70V as required (see Figures 2, 3, 4, 5 and 
Table 4). 

 

GROUNDING:  

Connect ground wire to backbox.  Install signaling appliance to backbox using mounting screws provided. 

WARNING:  THE SPEAKER STROBE APPLIANCE MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL BEFORE IT IS 

INSTALLED.  THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT 
SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR 
DEATH TO YOU AND/OR OTHERS. 

 

Figure 4: Jumper plug is used to select tap settings which = dBA loudness.

 

Figure 5: Tap Settings (Factory setting is 70V @ 0.5W (H)) 

  A  B  C  D

  E  F  G  H  I

  J

 J1

 

A

 

B

 

C

 

D

 

E

 

F

 

G

 

H

 

I

 

J

 

 

Each letter corresponds to a plug position of the header located on the printed 

circuit board.  Select voltage and wattage as shown in Table 3. 

NOTE

:  Use needle nose pliers to pull and properly insert the jumper plug to the desired tap setting. 

 

Table 3:  Speaker Voltage and Wattage Connection Chart 

Position 25V  70V 

A 8 

------ 

B 4 

------ 

C 2 

------ 

D 1 8 

E 1/2 4 
F 1/4 2 

G 1/8 1 
H ------ 

1/2 

I ------ 

1/4 

J ------ 

1/8 

P84478 G 

Sheet 2 of 4 

Reviews: