SPECIAL
ORDER
M1000 EMNA 06/06
Refer to the products Installation Instructions for proper
installation, wiring procedures and any additional
specifications.
Operational and Storage Specifications:
Temperature Range: 32°F - 120°F (0°-49°C)
Humidity Range: 0-85% Non-Condensing
Military and Government Systems offered by Wheelock…
Wheelock systems meet all requirements of the Unified Facilities Criteria (UFC)
4-021-01, 18 December 2002
UFC Performance Criteria for Mass Notification System for the Interior of Structures
Personnel Alert Systems (PAS)
Provide force protection and early warning in emergency situations including:
Bomb Threat, Terrorist Attack, Security Breach, Chemical Release, Natural Disaster
and OEM
Wheelock Wireless Platform for Base Wide (exterior) and Building Facility
(interior) Systems
Mass Notification Systems (MNS)
Secure Systems for SCIF room applications
Contact your Wheelock representative for additional information regarding base or
facility site visits and equipment recommendations.
SPECIFICATIONS AND ORDERING INFORMATION
For additional specifications, refer to the following data
sheets:
S0310
Series ET Speaker Strobes
S1610
Series E Speaker Strobes
S9020
Series RSS Colored Lens Strobes
S7000
Mounting Accessories
Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc.
standard terms and conditions.
Model Number
Order
Code
Lens
Color
Strobe
Candela
Mounting
Options
Strobe
Voltage
Strobe Current (RMS)
Agency
Approvals
note 1
note 2
16 vdc
24 vdc
RSSPA-24MCC-NW
3308
AMBER
MCC
wall or ceiling
24 vdc
note 3
none
RSSPB-24MCC-NW
3306
BLUE
MCC
wall or ceiling
24 vdc
note 3
none
RSSPG-24MCC-NW
3307
GREEN
MCC
wall or ceiling
24 vdc
note 3
none
RSSPR-24110-NW
3309
RED
110
wall or ceiling
24 vdc
0.420
0.37
UL, CSFM, MEA, BFP
E70-24MCW-FW
9023
CLEAR
MCW
wall
24 vdc
note 4
UL, CSFM, MEA, BFP
ET70-24MCW-FW
9021
CLEAR
MCW
wall
24 vdc
note 4
ISP2-W
3195
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SBL2-W
6989
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Note 1. Candela is measured on axis per UL 1638. Models with MCC
strobes have 4 field selectable candela settings. MCC settings are
rated for clear lens - derate approximately 25% for amber, 55% for
green and 70% for blue
Note 2. All strobes operate from 16 to 33 volts at 1 flash/second using
filtered or full-wave-rectified DC voltage (See Installation Instructions)
Note 3. Strobe Current for MCC Strobes:
MCC setting
15
30
75
95
current @ 16 vdc
0.065
0.105
0.189
0.249
current @ 24 vdc
0.045
0.070
0.119
0.159
Note 4. Strobe Current for MCW Strobes:
MCW setting
15
30
75
110
current @ 16 vdc
0.062
0.102
0.192
0.265
current @ 24 vdc
0.041
0.065
0.116
0.155
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
273 Branchport Avenue
Long Branch, NJ 07740
Phone: (800) 631-2148
Fax: (732) 222-2588
www.cooperwheelock.com