WARNING:  THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING 

FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE.  DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.   

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE 

VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES.  THE 
MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.   

 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE 

SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, APPLIANCE CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK POWER 
SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS 
TO WHICH THESE APPLIANCES ARE WIRED.  OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS 
OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

CAUTION:  

The NS Series horn/strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 

CANDELA AND SOUND OUTPUT SETTINGS: 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.  

WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE.  AFTER CHANGING 
THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.  IMPROPER SETTING OF THE 
CANDELA SELECT SWITCH MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH COULD RESULT IN A CURRENT DRAW 
EXCEEDING THE POWER SUPPLY’S CAPACITY. 

 

Figure 1: Showing Location of Jumper Plug and Candela Selector. 

30

95

15

75

177

115

MCC CANDELA POINTER

MCCH CANDELA POINTER

 

 

 

 

 

 

NOTE

:  Factory setting is on High dB, Code 3 and 15cd for MCC; 177cd for MCCH. 

NOTE:

  The NS must be set for Code 3 horn when installed on a synchronized notification appliance circuit (NAC). 

 

Figure 2:  Jumper plug settings for 

High dB and Code 3. 

Figure 3:  Jumper plug settings for Low 

dB and Continuous Horn. 

Figure 4:  Jumper plug settings for 

High dB and Continuous Horn. 

Figure 5:  Jumper plug settings for Low 

dB and Code 3. 

 

SHOWN 

SET ON 

HI dB 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON 

 CODE 3

 

(Use needle nose pliers to pull and 

properly set the jumper plugs.)

 

 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON

 CONT' HORN *

SHOWN 

SET ON 

LOW dB

 No jumper plugs are needed for 

Continuous Horn and low dB settings.  

However, it is recommended that the 

jumper plug be retained in the unit for 

future use (if needed) as shown.

 

 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON

 CONT' HORN *

SHOWN 

SET ON 

HI dB 

 

 

 

CENTER PIN 

 IS NOT USED

SHOWN 

SET ON 

LOW dB

 SHOWN 

 SET ON 

 CODE 3

 

 

P84794 F 