
Figure 3: Switch Settings
POS 1
POS 2
POS 3
POS 4
SLIDE HERE FOR (1)
SLIDE HERE FOR (0)
USE A SMALL SCREWDRIVER TO
CHANGE THE SWITCH POSITION.
WARNING: DOUBLE CHECK THE SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT. IMPROPER SETTINGS CAN
DAMAGE THE UNIT OR RESULT IN NO SOUND OUTPUT OR A dBA SOUND OUTPUT LEVEL THAT IS BELOW THE 75dB MINIMUM CODE
REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION. THIS COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
STEP 2:
Set desired alarm tone as follows (refer to Figure 2 and Table 6). Multitone Strobe Appliances are field set for any one of eight alarm tones by setting a four-position
switch (SW1) as shown in Figure 3 and Table 6. Use SW1 POS 2, 3, 4 to select the desired alarm tone.
Table 6: Switch Settings
Tone
POS 2
POS 3
POS 4
Horn 1
1
1
Bell 1
0
1
March Time Horn
0
0
1
Code 3 Horn
1
1
0
Code 3 Tone
0
1
1
Slow Whoop
0
1
0
Siren 1
0
0
HI/LO 0
0
0
NOTE:
The Code 3 Horn and Code 3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency evacuation
signaling. They should be used only for fire evacuation signaling and not for any other purpose.
The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently. All other
tones are recommended for use only on continuous (non-coded)
CAUTION:
Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off..
WIRING DIAGRAMS:
Figure 4:
1. Multitone Strobe models have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at
each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in Figure 4. The polarity
shown in the wiring diagrams is for operation of the appliances. The polarity is reversed by the FACP during supervision.
Figure 5:
Audible appliance and strobe operate independently.
-
+
AUDIBLE
STROBE
TO NEXT
AUDIBLE OR
END OF LINE RESISTOR
TO NEXT
STROBE OR
EOLR
FROM PRECEDING
AUDIBLE OR FIRE ALARM
CONTROL PANEL (FACP)
FROM PRECEDING
APPLIANCE OR FIRE ALARM
CONTROL PANEL (FACP)
+
-
+
-
+
-
+
-
+
-
(EOLR)
Figure 6:
Audible appliance and strobe operate in unison.
Red and black shunt-wires are supplied.
GND.
FROM PRECEDING
APPLIANCE OR
FIRE ALARM CONTROL
PANEL (FACP)
STROBE AUDIBLE
-
+
-
+
TO NEXT
APPLIANCE OR
END OF LINE
RESISTOR (EOLR)
BLACK
RED
(+) (-)
(+) (-)
P84870E
Sheet 4 of 6