background image

Manual Operating Controls

The operating controls for the sectionalizer are located
on the underside of the operator mechanism housing, as
shown in Figure 4.

Manual Opening

The hookstick-operated, manual opening pullring trips
open the sectionalizer with one pull of the yellow pullring.

One-Count-To-Open Lever

The one-count-to-open lever provides the capability of
opening the sectionalizer on the first overcurrent interrup-
tion count. It provides for added safety during downline
hot-line work without disturbing the normal counts-to-
open setting of the sectionalizer. The hookstick-operated
lever locks into position when pulled down, and must be
manually reset to restore normal counts-to-lockout.

Manual Closing

The hookstick-operated, manual closing pullring closes
the sectionalizer when the gray pullring is pulled down
approximately 10 to 12 times. The pullring manually
charges the closing springs and overtoggles the springs
to initiate the closing. (When the sectionalizer closes,
the resistance on the pullring is eliminated.) This is the
only means of closing the sectionalizer.

Auxiliary Power

Auxiliary power (120 Vac, 25 VA, min.) is required for the
cabinet heater and/or potential charging of the trip
capacitor. The input receptacle is located on the underside
of the operator cabinet (Figure 4). A mating connector
plug is also provided with the unit.

Indicating Devices

A contact position indicator and an operations counter
are located under the sleet hood of the operator cabinet.

The yellow contact position indicator is pinned to the
main operating shaft of the sectionalizer to indicate the
OPEN and CLOSED condition of the main contacts.

The operations counter gives a visual indication of the
cumulative number of openings of the unit.

Type GV and GW Installation Instructions

6

Figure 4.
Operating controls on the underside of the operator cabinet.

84575KMA

Provision for
installing auxiliary
switch wiring
receptacles

Manual
Opening
Pullring

120 Vac input
receptacle

(mating plug
also furnished)

Manual closing

pullring

One-count-to-

open Lever

OPERATING CONTROLS AND SETTINGS

IMPORTANT:

The potential charging board also includes

a voltage restraint feature which prevents the unit from
counting overcurrent interruptions unless the auxiliary
voltage is also interrupted. Therefore, the auxiliary power
must be obtained from the load side of the backup
protective device so that the board is energized only
when the backup is closed. Failure to follow this pre-
caution will prevent proper operation of the sectionalizer.

WARNING: 

Do not rely on the open position of

the yellow operating handle; it does not ensure

that the line has been de-energized. Always establish
a visible disconnect. Failure to follow proper safety
practices can result in contact with high voltage, which
will cause death or severe personal injury.

G116.0

!

WARNING: 

Always use a hotstick when work-

ing with this equipment. Failure to do so could

result in contact with high voltage, which will cause
death or severe personal injury.

G108.1

!

Summary of Contents for Kyle GV

Page 1: ...nalizer 9 Mounting the Sectionalizer 9 Grounding the Sectionalizer 9 High Voltage Connections 11 120 Vac Wiring 11 Internal Wiring 12 Auxiliary Switch 13 Operating Instructions 15 Initial Operation 15...

Page 2: ...this equipment carefully read and understand the contents of this manual Improper operation handling or maintenance can result in death severe personal injury and equipment damage G101 0 SAFETY FOR LI...

Page 3: ...d keep the operator cabinet closed to protect the electronic control components Standards Kyle sectionalizers are designed and tested in accor dance with ANSI standard C37 63 where applicable Quality...

Page 4: ...g A 400 400 Rated symmetrical interrupting current A rms 880 880 Rated making current asymmetrical A rms 20000 15000 Short time ratings A rms 10 seconds symmetrical 4000 3500 1 second symmetrical 1250...

Page 5: ...tors No 6 solid 350 MCM 305 12 1203 47 25 435 17 329 13 562 22 Ground Connector No 8 No 2 Figure 2 Type GW Sectionalizer 254 10 203 8 Terminal Connectors No 6 solid 350 MCM Ground Connector No 8 No 2...

Page 6: ...d an operations counter are located under the sleet hood of the operator cabinet The yellow contact position indicator is pinned to the main operating shaft of the sectionalizer to indicate the OPEN a...

Page 7: ...phase current resis tors are listed in Table 3 Ground current resistors are identified with the ground sym bol and the actuating current value in amperes Catalog numbers for the available ground curr...

Page 8: ...gh the sectionalizer is restored and the overcurrent has been determined to be inrush current The three second time interval allows for system inrush parameters to stabilize prior to allowing the sens...

Page 9: ...ng height is equal to or greater than the distance between lifting lugs See Figure 8 Mounting the Sectionalizer Figures 9 and 10 show installation using Kyle mounting frames If other mounting means ar...

Page 10: ...13 473 mm 18 5 378 mm 14 5 432 mm 17 244 mm 9 5 383 mm 15 25 324 mm 12 75 699 mm 27 5 622 mm 24 5 489 mm 19 25 508 mm 20 244 mm 9 75 383 mm 15 Figure 10 Mounting hardware for Type GV sectionalizer 62...

Page 11: ...and the cover of the GW sectionalizers will accept No 8 through No 2 stranded wire 120 Vac Wiring A 120 Vac source voltage is required if the mechanism cabinet heater and the potential charger for th...

Page 12: ...One Count Switch G RED YEL G C B A A C B C T Protector NC NO C Count Reset Switch Zenar Diode Zenar Diode A B C D E F 1 Potential Charger Board ORG YEL GRN WHT BLK WHT 2 4 3 Heater D B BLK WHT 120 Va...

Page 13: ...he switch link by removing the groove pin and C rings 3 Remove the machine screws attaching the assembly to the cabinet 4 With the switch removed unfasten the two hex nuts and lockwashers from the lon...

Page 14: ...punch mark on the shaft are in vertical plane with the punch mark in the end plate as shown TERMINALS 3 7 11 15 CAMS TERMINALS 1 5 9 13 TERMINALS 2 6 10 14 TERMINALS 4 8 12 16 CONTACTS SQUARE SHAFT CA...

Page 15: ...e work the sectionalizer can be programmed for one count to open without opening the operator mechanism housing and disturbing the normal operating settings The one count to open lever overrides the C...

Page 16: ...performing the following tests monitor the conti nuity between test points C and D on the circuit board see Figure 6 If no continuity exists between either set of test points upon closing of the secti...

Page 17: ...sibility of a false count the phase sensing portion of the sectionalizer control circuit should be disabled when the ground minimum actuating current is being checked The following procedure is used 1...

Page 18: ...lso inter rupted To check the voltage restraint feature proceed as follows 1 Jumper the ground actuating resistor with a short lead to disable the ground sensing circuit 2 Jumper terminals P and D tog...

Page 19: ...normally For an inrush current condition the phase and ground minimum actuating current detection is blocked for three seconds to prevent counting the inrush current The three second time interval al...

Page 20: ...y Street Pewaukee WI 53072 USA www cooperpower com 2005 Cooper Power Systems or its affiliates Kyle is a registered trademark of Cooper Power Systems or its affiliates KA2048 101 Rev 01 SAFETY FOR LIF...

Reviews: