Module Installation
Ensure power to the receptacle has been disconnected before beginning
to remove/mount the receptacle.
1. Remove the shorting or open cap if supplied with the luminaire.
Note: Receptacle caps, if supplied with the luminaire, are used for closing or opening the socket circuit. In addition,
these caps can offer weatherproof protection for the receptacles that are not yet fitted with the WOLC Module.
WOLC Modules can be installed on luminaires that feature ANSI C136.41-
compliant receptacles.
3
2. Place the WOLC Module firmly into the receptacle (not supplied by Cooper
Lighting Solutions) and twist it clockwise (Install arrow) until it locks in place.
Overview
The Cooper Lighting Solutions WaveLinx Outdoor Lighting Control (WOLC)
Module extends the WaveLinx System’s controls capability to a building’s
surroundings or site such as parking lots and short pathways.
The WOLC Module is individually addressable and installs on top of a light pole
via an ANSI136.41-compliant, 7-pin twist-lock connector. It can switch
luminaires ON/OFF via an integrated high current relay, dim luminaires
equipped with 0-10V dimming drivers or ballasts. It communicates with the
WaveLinx Wireless Area Controller over an IEEE 802.15.4 network.
Important Safeguards
When using electrical equipment, basic safety precautions should always
be followed including the following:
—
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
—
Do not let power supply cords touch hot surfaces.
—
Do not mount near gas or electric heaters. Equipment should be mounted in
locations and at heights where it will not readily be subjected to tampering
by unauthorized personnel.
—
The use of accessory equipment is not recommended by Cooper Lighting
Solutions as it may cause an unsafe condition.
—
Do not use this equipment for other than the intended use.
SAVE THESE INSTRUCTIONS
Note
Tip
!
STOP
Note
Tip
!
STOP
Part Number
WOLC-7P-10A
2
Ratings
Voltage
—
Operating voltage: 120-347Vac;
50/60 Hz
Load Rating
—
120-347Vac E-Ballast; 10A
—
120-347Vac Resistive; 10A
—
120-347Vac Tungsten; 10A
—
120-347Vac General Purpose; 10A
Interface
—
Dimming: 0-10V; 10mA
(IEC 60929 Annex E)
Environmental
—
Ambient temperature range:
-40°C to +65°C
—
Protection classification: IP66
—
Relative humidity: up to 95%
non-condensing
Listings
—
UL: UL916/773
(File # E222633 USA and Canada)
Communication
—
Wireless Protocol: IEEE 802.15.4
—
Radio Frequency: 2.4 GHz
—
Transmit Power: 20dBm
—
Distance: 150ft (45m) line of site
between modules
Note
Tip
!
STOP
BLACK: Line In
RED: AC to Driver
GREY/-: Control to Driver
VIOLET/ +: Control to Driver
WHITE: Neutral
ORANGE: Unused
BROWN: Unused
3. Mount the control with the arrow and ‘N’ on the cover facing north.
Note: The receptacle assembly may have to be rotated to face north.
Receptacle
Control Module Cap
O
RG
P
ow
er
B
R
N
In
pu
t
GR
Y(-
)/0
-1
0V
VI
O
(+
)/0
-1
0V
O
RG
P
ow
er
B
R
N
In
pu
t
GR
Y(-
)/0
-1
0V
VI
O
(+
)/0
-1
0V