1. Mount Low-Voltage Power Module
Min. 3”
(75mm)
Min. 36”
(900mm)
Min. 18”
(450mm)
2. Provide Power
All new wiring must be fully verified before applying power.
MAX Ampacity (Amps)
Normal
Power Input
EM
Power Input
Single Panel
Input Only
120VAC 277VAC 120VAC 277VAC 120VAC 277VAC
LVPM-12-100-64-2E
9
4
1.8
0.8
10.8
4.8
Normal Power
input only
Normal Power
with Centralized EM
remove divider
and wire internally
normal power
emergency power
connection
normal power
connection
normal power
transfer
switch
normal
power
emergency
power
emergency
panel
3. Connect Fixtures
ALERT
7
8
9
10
11
12
1
2
3
4
5
6
TEST
RESET
UNPAIR
IDENTIFY
DIAG
STATUS
EMERGENCY
57VDC
90W MAX
(EACH OUTPUT)
CAUTION: DO NOT OVERLOAD
LOW VOLTAGE OUTPUTS
SUITABLE FOR CLASS 2 WIRING
LL5030
16EN
Connect 90W MAX per LV output
MAX light fixtures per power module = 36
Dip switches not used
Assure all are in OFF position
Low-voltage
lighting cable
1
2
3
4
5
6
O
F
F
1200W Power Module
WaveLinx Low-Voltage
IB503054EN
page 2