Cooper Lighting DLC-PDC Installation And Operation Instructions Manual Download Page 8

CALIBRATION 

The general theory behind ON and OFF setpoint calibration is to set the ON setpoint at a lower 
footcandle level than the OFF setpoint. This way, the controlled lights will not switch OFF during a 
period when they should be ON. The difference between the ON and OFF setpoints is called the 
Deadband. In general, the deadband should be large enough (about 10% of the expected calibration 
range) to provide system stability. 

In a dusk-to-dawn lighting application, it is important to have a deadband sufficient to prevent 
confusing the control board as the desired setpoint is reached. To insure that lights are ON when 
needed, the deadband should be biased to leaving the lights ON longer rather than switching them 
OFF too soon. 

4.1 

Dusk-To-Dawn Calibration Procedure 

The Dusk-To-Dawn technique of calibration has been developed that, when followed, will work well 
for most calibration needs.  Additionally, if you have a different lighting application other than dusk-to-
dawn, you should be able to discern the method of this technique and apply it to your situation. 

The DLC-PD sensors have a very linear response which makes it simple to predict the setpoints of 
the DLC-PDC Controller.  Use of non-GREENGATE/

COOPER LIGHTING SOLUTIONS

 sensor 

will likely make this task more difficult. 

This procedure has been created in such a manner as to not require any sophisticated calibration 
equipment.  Shown below are the tools needed for Dusk-To-Dawn calibration of the DLC-PDC. 

TOOLS NEEDED:

SMALL FLATHEAD SCREWDRIVER 1/8” 

PROCEDURE:  begin this procedure just before dawn

1.

Switch the Input Delay Switch OFF (UP).

2.

At the time during dawn when the daylight is at the level where you would want the lights to
switch ON at dusk, turn both the High Level Setpoint and the Low Level Setpoint trimpots all
the way counter clockwise so that both setpoint LEDs are ON.  The Relay Status LED will be
ON and the lighting circuit will be OFF.

3.

Turn the Low Level Setpoint trimpot clockwise to the point that the Low Level Setpoint LED
switches OFF.  The Relay Status LED and lighting circuit will remain unchanged.

4.

Wait for a period of time for the light level to increase (the Low Level Setpoint LED will switch
back ON), and adjust the High Level Setpoint trimpot clockwise to the point that all LEDs
switch OFF.  The DLC-PDC should now be calibrated for a dusk-to-dawn application.

5.

Return the Input Delay Switch to the ON (DOWN) position.  Note; the lights will switch Off at
dawn, but if a greater deadband is required set the High Level Setpoint trimpot ahead of the
Low Level Setpoint trimpot (adjust as required).  Should the Dusk-to-Dawn lighting cycle fail
to switch the lights ON and OFF as planned, please refer to the Troubleshooting section of
this manual.

Summary of Contents for DLC-PDC

Page 1: ...DLC PDC PHOTODIODE CONTROLLER INSTALLATION AND OPERATION INSTRUCTIONS 1121 Highway 74 South Peachtree City GA30269 Customer Service Telephone 800 553 3879 Fax 800 954 7016 DLC PDC Rev 2...

Page 2: ...DELAY SWITCH 6 3 6 SEQUENCE OF OPERATION 7 4 CALIBRATION 8 4 1 DUSK TO DAWN CALIBRATION PROCEDURE 8 4 2 FOOTCANDLE SETTINGS GUIDE 9 5 SPECIFICATIONS 10 6 MAINTENANCE 11 7 DLC PDC TROUBLESHOOTING GUID...

Page 3: ...ations of the sensor including but not limited to the indoor outdoor atrium and skylight types 1 2 Overview The DLC PDC Photodiode Controller automatically switches a dry contact in response to change...

Page 4: ...nnected to Terminal 4 see Figure 1 2 2 Load Connections The DLC PDC Form C output has Common connected to Terminal 7 LOAD RATING 3A MAX the Normally Open contact is connected to Terminal 6 and the Nor...

Page 5: ...dicator LEDs switch functions control options and sequence of operations 3 1 High Level Setpoint and LED Indicator The top trimpot labeled OFF see Figure 2 sets the High Level Setpoint which is the le...

Page 6: ...ator The third LED located beneath Terminal 8 See Figure 2 indicates the status of the DLC PDC s relay If the LED is lit the relay is energized Since this is a normally closed relay energizing the rel...

Page 7: ...the day as the sensor light level increases to the maximum light level and then starts to decrease towards dusk As the light level passes through the High Level Setpoint the High Level Setpoint LED wi...

Page 8: ...ask more difficult This procedure has been created in such a manner as to not require any sophisticated calibration equipment Shown below are the tools needed for Dusk To Dawn calibration of the DLC P...

Page 9: ...0Fc 1000Fc 1200Fc 1400Fc 1600Fc 1800Fc 2000Fc Table 1 DLC PD Sensor Footcandle Chart EXAMPLE 1 If a DLC PD OT Outdoor sensor is providing the input signal and it is desired to switch lights ON at 30 F...

Page 10: ...C Input Sensor Type DLC PD Photodiode 3 wire Input Time Delay 30 seconds may be overridden with the Input Time Delay Switch Dead Band Adjustable 5 95 Operating Temperature 12 F to 140 F 11 C to 60 C A...

Page 11: ...11 6 MAINTENANCE Every 6 months inspect the wiring for broken or frayed connections Occasionally wipe clean the plastic enclosure Figure 4 DLC PDC WIRING CONNECTION DIAGRAM...

Page 12: ...12 Figure 5 DLC PDC AND OCCUPANCY SENSOR CONNECTION DIAGRAM...

Page 13: ...s exposed to bright light the reading should be approximately 10VDC Faulty Controller Examine the gross functionality of the DLC PDC by doing the following 1 Turn off the Input Time Delay Switch 2 Dis...

Reviews: