Cooper Crouse-Hinds LP1 Series Installation & Maintenance Information Download Page 4

OPENING COVER

LP1 and LP2 Series panel boards are furnished with captive
stainless steel bolts. Make sure all cover bolts are fully retracted
into the cover before attempting to open or close the cover.

After all bolts are fully disengaged, firmly grasp the bottom and right
side of the cover and carefully swing cover aside. To prevent
damage to the ground joint surface, avoid striking cover, or devices
in cover, on neighboring enclosures or structures.

REMOVING AND REINSTALLING
PANEL BOARD COVER

Loosen all cover bolts and open cover. Using the hinge
sections still attached to the cover, grasp the cover under
opposite edges and lift from body.

To replace cover, make sure cover and body ground joint
surfaces are clean and not scratched. Orient cover so hinge
side of cover will align with hinge on body. Lift cover to
approximate position, and line up. Avoid sliding cover ground
joint surface over ground joint surface of body. Cover / body
bolt holes must match up. Hand start the corner bolts. Fully
tighten all cover bolts (torque to 25-30 ft. lbs.). Follow
procedures in Opening Cover section once hinges are
reinstalled.

ACCESS TO CIRCUIT BREAKER ENCLOSURE

1. For panel boards with alternate feed, pull wires into the

enclosure so that they are long enough to make the required
connections. Make connections per Figure 2 for either single or
three phase circuits. An EYS type seal will need to be installed
for this 3” entry to meet the NEC requirements.

When adding or removing circuit breakers, the final
configuration should begin with position #1 through the total
number of spaces used without leaving intermittent spaces. This
is done to ensure the panel board is evenly loaded by phase.
Use bolts on the bus bars to fasten the line side of each breaker
added. Connect the load side of each breaker to the appropriate
wire after cutting it to correct length.

2. Test wiring for correctness with continuity checks and for

unwanted grounds with an insulation resistance tester.

3. Align main circuit breaker operator with toggle position of the

main circuit breaker. Be sure all bolts are retracted into the
flange. Close cover and securely tighten all cover bolts. Use
only bolts supplied with the panel board. Torque all cover bolts
to 25-30 ft. lb.

4.

Mark circuit card directory located on junction box cover with
appropriate descriptions for each branch circuit number. Place
circuit card directory inside clear plastic jacket before inserting
in its holder.

NOTE: LP Series panel boards must be protected during hose down
operations. These panel boards are watertight but the breathers
and drains are not hose tight.

GROUND FAULT CIRCUIT BREAKER (GFCB)
INSTALLATION INSTRUCTIONS

Connect the GFCB line neutral pigtail(s) to the breaker housing
isolated neutral block. This block is mounted to the chassis in the
upper right section.

Select the load lead(s) on the branch terminal block in the terminal
housing that correspond(s) to the circuit location number in the
breaker housing (circuit numbers 2,4,6,8,10 or 12); ring out to locate
the same wire(s) in the breaker housing and insert into breaker
terminal. Do not tighten breaker terminal screw at this time (on 2-
pole breakers, tighten one terminal screw).

Selecting the highest available branch terminal block number
ensures the maximum breaker capacity in the panel board.

Ring out to locate same wire in the breaker housing and connect it
to the GFCB load neutral terminal.

Record the GFCB location and designation numbers (

G2, G4, G6,

G8, G10, G12

) on the Breaker Directory Card.

Place GFCB designation sticker (

G2, G4, G6, G8, G10, G12

) on the

lockout plate. Note that there is a stagger between the GFCB
push-to-test and the operator handle. For example, the test button
for circuit number 2 should be labled “G2” and it is positioned next
to operator handle for circuit number 4. Similarly, “G4” is next to
circuit number 6, etc.

GROUND FAULT CIRCUIT BREAKER TESTING
PROCEDURE

To test a single GFCB:

1.

With GFCB circuit energized push the corresponding button for
that circuit.

2.

Note if GFCB handle indicated trip or check if power was cut off
on that circuit.

3.

Reset GFCB

Note:

If adding GFCB breakers in the field, use only Cutler-

Hammer QBGF or QBGFEP series for GFI or EPD applications
respectively in Class I, Group C, D areas. For Class I, Group B
areas, use QBHGF or QBHGFEP breakers for GFI or EPD
applications respectively.

CAUTION

To maintain the integrity of the enclosure, clean dirt or foreign

material from both flange surfaces of body and cover before

closing. This will ensure a proper explosionproof joint.

IF 1433 • 04/03

Copyright © 2003, Cooper Industries, Inc.

Page 4

CAUTION

Per manufacturer’s instructions for maximum protection against

electrical shock hazard, operate test circuit on the unit at least

once a month.

CAUTION

To maintain the integrity of the enclosure, hammers or prying tools

must not be allowed to damage the flat joint surfaces. Do not

handle cover roughly, or, if removed, do not place it on surfaces

that might damage or scratch the flat ground joint surfaces.

CAUTION

DO NOT use cover bolts or circuit breaker operators as a means to

lift the enclosure. Excessive force on the fully retracted bolts or

operators may damage the shaft or bolt.

CAUTION

Panel board covers weigh up to approximately 50 to 55 lbs.

To avoid injury, handle appropriately for this weight.

Summary of Contents for LP1 Series

Page 1: ...l as in damp wet locations indoors or outdoors LP2 Series panel boards are designed for use in Class I Div 2 Groups B C D Panel boards should be installed inspected maintained and operated by qualified and competent personnel Read entire instructions before starting installation of this product Contact your Crouse Hinds Sales Representative Crouse Hinds Customer Service or your Crouse Hinds Distri...

Page 2: ...ons using typical wiring diagrams per Figure 2 Terminal Housing Conduit 2 Conduit 2 Cl 1 Div 1 Grp C D Within 18 Within 18 Cl 1 Div 1 Grp B C D Within 18 Within 18 Cl 1 Div 2 Not required Not required CAUTION To prevent external fire or explosion external conduit sealing fittings are required on all conduit entrances within 18 of the enclosure for enclosures when used in Class I Group B hazardous ...

Page 3: ... 17 21 25 29 33 34 30 26 22 18 14 12 10 8 6 4 2 5 27 31 35 36 32 28 24 20 16 12 N 10 N 8 N 6 N 4 N 2 N 1 3 11 15 19 23 7 9 13 17 21 25 29 33 34 30 26 22 18 14 12 10 8 6 4 2 5 27 31 35 36 32 28 24 20 16 12 N 10 N 8 N 6 N 4 N 2 N C C SIZE PANEL ONLY PASSTHRU MCB MLO A B C W O GFI W GFI 2N 12N W O GFI W GFI 2N 12N A B A B C 2N N 6N N 8N N 4N N 10N N 12N N 2N N 6N N 8N N 4N N 10N N 12N N NEUTRAL C SIZ...

Page 4: ...rtight but the breathers and drains are not hose tight GROUND FAULT CIRCUIT BREAKER GFCB INSTALLATION INSTRUCTIONS Connect the GFCB line neutral pigtail s to the breaker housing isolated neutral block This block is mounted to the chassis in the upper right section Select the load lead s on the branch terminal block in the terminal housing that correspond s to the circuit location number in the bre...

Page 5: ...s operator plugs Changing present breaker pole combinations is solved by choosing the appropriate kit Before adding or removing any breakers see OPENING COVER section If adding breakers determine the quantity trip rating and number of poles for each Add or remove circuit breakers as necessary For Group B applications use only Cutler Hammer QBHW series for conventional breakers GFI EPD breakers are...

Page 6: ...t is tight against cover interior using the LP K2 replacement cover plugs Securely tighten all cover bolts Use only bolts supplied with the panel board Start cover bolt threads by hand then torque all cover bolts to 25 30 ft lbs PANEL BOARD REPLACEMENT PARTS CAT NUMBER DESCRIPTION LP K1 Extra circuit breaker operator assemblies for single pole circuit breakers qty 3 LP K2 Replacement cover plugs f...

Page 7: ...t le Code canadien de l électricité CCE ainsi que pour les emplacements intérieurs ou extérieurs humides et mouillés Les tableaux de la série LP2 sont conçus pour l utilisation dans les emplacements de Classe I division 2 groupes B C et D Les tableaux doivent être installés inspectés entretenus et exploités par du personnel qualifié et compétent Lisez attentivement toutes les instructions avant d ...

Page 8: ...1 gr C et D Moins de 18 po Moins de 18 po Cl 1 div 1 gr B C et D Moins de 18 po Moins de 18 po Cl 1 div 2 Non exigé Non exigé ATTENTION Pour éviter le risque d incendie ou l explosion externes des coupe feu antidéflagrants externes sont exigés à toutes les entrées de conduits à moins de 18 po du boîtier pour les boîtiers dans les emplacements dangereux de Classe I groupe B Utilisez des coupe feu C...

Page 9: ... 29 33 34 30 26 22 18 14 12 10 8 6 4 2 5 27 31 35 36 32 28 24 20 16 12 N 10 N 8 N 6 N 4 N 2 N 1 3 11 15 19 23 7 9 13 17 21 25 29 33 34 30 26 22 18 14 12 10 8 6 4 2 5 27 31 35 36 32 28 24 20 16 12 N 10 N 8 N 6 N 4 N 2 N C Tableau de calibre C seulement Passage MCB MLO A B C Sans GFI Avec GFI 2N 12N Sans GFI Avec GFI 2N 12N A B A B C 2N N 6N N 8N N 4N N 10N N 12N N 2N N 6N N 8N N 4N N 10N N 12N N Ne...

Page 10: ...ent Placez le répertoire des circuits dans la chemise en plastique transparent avant de l insérer sur son support NOTA Les tableaux de la série LP doivent être protégés pendant les opérations d arrosage au boyau Les panneaux sont étanches mais les évents et les purgeurs ne le sont pas INSTRUCTIONS D INSTALLATION DES DISJONCTEURS DE FUITE À LA TERRE GFCB Reliez les raccords flexibles neutres du GFC...

Page 11: ...actionneurs de disjoncteurs servent à modifier la configuration d un tableau LP K1 comprend des actionneurs pour disjoncteurs unipolaires et LP K3 des actionneurs pour disjoncteurs GFI EPD bipolaires et tripolaires tandis que LP K2 comprend des bouchons d obturation Il suffit de choisir l ensemble approprié pour modifier la combinaison actuelle des pôles de disjoncteurs Avant d ajouter ou d enleve...

Page 12: ...actionneur à l aide de la rondelle de blocage et de la vis fournies de manière que le contre alésage soit tourné vers le haut et que l extrémité courte soit tournée vers le centre du compartiment de disjoncteurs AJOUT DE BOUCHONS Enlevez l actionneur du disjoncteur et à l aide d un lubrifiant pour filets à base de produits non pétroliers vissez le bouchon jusqu à ce qu il soit serré contre l intér...

Page 13: ...así como en lugares interiores y exteriores mojados y húmedos Los tableros Serie LP2 están diseñados para utilizarse en Clase I Div 2 Grupos B C D Los tableros deben instalarse inspeccionarse mantenerse y operarse por personal calificado y competente Lea todas las instrucciones antes de empezar la instalación de este producto Si tiene cualquier duda llame a su Representante de Ventas Crouse Hinds ...

Page 14: ...zando los diagramas típicos del alambrado de la Figura 2 Cubierta de la Terminal Tubería 53 2 Tubería 53 2 Cl 1 Div 1 Grp C y D Dentro de 46 cm Dentro de 46 cm Cl 1 Div 1 Grp B C y D Dentro de 46 cm Dentro de 46 cm Cl 1 Div 2 No se requiere No se requiere PRECAUCIÓN Para prevenir fuego exterior o explosión los accesorios para sellar la canalización de tubería externa se requieren en todas las entr...

Page 15: ...21 25 29 33 34 30 26 22 18 14 12 10 8 6 4 2 5 27 31 35 36 32 28 24 20 16 12 N 10 N 8 N 6 N 4 N 2 N 1 3 11 15 19 23 7 9 13 17 21 25 29 33 34 30 26 22 18 14 12 10 8 6 4 2 5 27 31 35 36 32 28 24 20 16 12 N 10 N 8 N 6 N 4 N 2 N C SOLO TABLERO TAMAÑO C Passthru MCB MLO A B C W O GFI W GFI 2N 12N W O GFI W GFI 2N 12N A B A B C 2N N 6N N 8N N 4N N 10N N 12N N 2N N 6N N 8N N 4N N 10N N 12N N NEUTRO SOLO T...

Page 16: ...io del circuito localizada en la cubierta de la caja de unión con las descripciones adecuadas para cada número de circuito derivado Coloque la tarjeta del directorio del circuito dentro de la cubierta de plástico transparente antes de insertarla en su contenedor NOTA Los tableros de la Serie LP deben estar protegidos durante las operaciones bajo manguera Estos tableros son herméticos al agua pero ...

Page 17: ...cos únicamente con interruptores Cutler Hammer como sigue INTERRUPTOR TERMOMAGNETICO 240 120 120 208 Vc a Corriente max A Tipo de interruptor Retroalimentación 100 BAB principal Derivado 35 GFI o EPD 30 QBHGF QBHGFEP 5 Nosotros recomendamos un programa de Mantenimiento Preventivo Eléctrico como se describe en el Boletín de la National Fire Protection Association NFPA No 70B ADICIÓN O REMOCIÓN DE I...

Page 18: ...o doble de la flecha de operación hasta que la bobina pequeña se asiente contra la porción del circuito de la flecha 5 Enrosque la flecha desde el interior de la envolvente por la entrada adecuada del operador hasta que ya no pueda girarse 6 Regrese la flecha una o dos vueltas para que el anillo elastomérico en forma de O no quede expuesto La sección cuadrada de la flecha debe estar encima de la s...

Reviews: