Cooper Crouse-Hinds GmbH
88888
Flameproof modules, series GHG 62. .... R....
Contact arrangement
additional devices
Signal contact
Aux. contact
S
Aux
10.3
Signal contact
Rated voltage:
up to 230V
Rated current:
5 A
Min. switching capacity:
5 mA at 24V
Making/braeking capacity I
e
/U
e
(IEC/EN62019):
AC 14
1 A / 400 V
2 A / 230 V
DC 12
1 A / 220 V
1,5 A / 110 V
DC 13
2 A /
60 V
4 A /
24 V
10.4
Auxiliary contact multi pole
Rated voltage:
up to 230V
Rated current:
5 A
Making/braeking capacity I
e
/U
e
(IEC/EN62019):
AC 14
1 A / 400 V
2 A / 230 V
DC 12
1 A / 220 V
1,5 A / 110 V
DC 13
2 A /
60 V
4 A /
24 V
10.2
RCBO with Circuit breaker; GHG625
Rated voltage:
Main contakt
up to 400 V AC
Aux./Signal contakt
up to 230 V AC
Rated current:
ELCB
up to 63 A
Circuit breaker
from 0.5 A up to 32 A (40 A)
Aux. contact
max. 5 A
Short-circuit protection:
up to 10 kA depend on circuit breaker
Back-up fuse:
ELCB
max. 100 A gL
Circuit breaker
dep. on rated current up to 100 A gL
Tripping current ELCB:
30 mA up to 500 mA
Component size:
2*
3*
4
Weight:
ca.
0,96kg
1,24kg
1,62kg
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.
Contact arrangement
ELCB with circuit breaker
1-pole + N
2-pole
10
Technical data the complete modules
10.1
ELCB (RCCB), 2 and 4-pole; GHG624
Rated voltage:
Main contact
230/400 V AC up to 240/415 V AC
Aux. contact
up to 230V AC
Rated current:
Main contakt
up to 63A
Aux.contakt
max. 5A
Short-circuit protection:
10 kA
Back-up fuse:
max. 100 A gG
Tripping current:
30 mA up to 500 mA
Component size:
2*
3*
4
Weight:
ca.
0,96kg
1,24kg
1,62kg
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
Contact arrangement - ELCB (RCCB)
2-pole
4-pole
10.5
Interface Relais R1561
Switching volta
min/max
12 V / 250 V AC
Switching currentge
min/max
10 mA / 6A
Braeking capacity
AC 1 min/max
0,6 VA / 1500 VA (ohmische Last)
DC 1 min/max
0,6 W / 140 W
Contact arrangement
ELCB with circuit breaker
and Interface Relais R1561