No. 3 ventilator OA interface

 

System confirm setting

 

Note: there is no priority between the multiple controller or the original stand-
ard intelligent controller, ventilator will execute instruction according to the  
later setting by either controller. 

Single Ventilator Setting

 

By press the Set button       to switch to the very ventilator, in the middle of the control-
ler it displays no. 1 to no. 16, at this time, can press the mode button shortly to switch 
to OA/RA/EA mode and set the fan speed by UP and DOWN button, after setting for 2 to 
3 seconds, control system will automatically confirm the setting. It is also available via 
the multi controller to set the heater temperature (only available in some of latest PCB).   

 

Timer On/Off Setting

 

The multiple controller can control all the ventilators on/off via timer function, it is al-
lowed to set on/off  2 periods per day, and 7 days per week, the function and setting is 
same like the touch screen intelligent controller, please refer to the manual.

 

Error Code 

The multiple controller displays error code when there is error of the ventilator, a symbol 
if     will be shown at the top left corner, by pressing SET button      to switch to different  
ID ventilator can check all the ventilator error status. Error code list as below.

 

Code

 

E1

 

Fresh air temperature 

sensor error

 

E2 

EEPROM error 

E3 

Return air temperature 

sensor error 

Error

 

E4 

 Exhaust air tempera-

ture sensor error  

E5 

Communication error 

E6 

Supply air temperature 

sensor error 

E7 

Exhausted fan error 

E8 

Supply fan error 

No. 3 ventilator error

 

Error Code E7

 

Summary of Contents for LH-13001

Page 1: ... INTELLIGENT CONTROLLER FOR ENERGY RECOVERY VENTILATION SYSTEM Thank you for choosing Cooper Hunter energy recovery ventilation system please read this service manual carefully before operation and retain it for future reference ...

Page 2: ...units switched the SW4 4 to the same Baud rate like the below figure A Note some PCB models have the Baud rate switch of 4800 or 9600 for the details please refer to the ventilator manual 2 Turn on the ventilator refer to the ventilator user manual set the correct ID address of each ventilator parameter number 08 available ID number from 1 to 16 refer to below figure B In the same network it is no...

Page 3: ...signal interference 4 Total length of communication wire should not be over 1km in order to minimize the signal attenuation please try to shorten the communication wire C02 S2 S1COMM1 AN4 AN3 AN1 AN2 B GND A 12V N L PORT 1 PORT 2 PORT 3 PORT 4 CN2 CN5 CN4 CN6 CN7 CN3 LD3 LD4 RLY8 CN EAFM CN EAFM CM DM CN9 CN11 CN12 CN8 CN10 SW4 CN25 CN13 CN SAFM PE CN86 CN85 C02 S2 S1COMM1 AN4 AN3 AN1 AN2 B GND A ...

Page 4: ...rameter number to be P0 fan mode setting at this time to press Mode button again enter P0 setting available value number from 0 to 2 which means 2 speeds control 3 speeds control and 10 speeds control Default value is 2 10 speeds control Use the Up and down button to change the value number press SET button again to confirm Note for the same BMS network it is suggested to connected all AC ventilat...

Page 5: ...re only available in some of latest PCB Timer On Off Setting The multiple controller can control all the ventilators on off via timer function it is al lowed to set on off 2 periods per day and 7 days per week the function and setting is same like the touch screen intelligent controller please refer to the manual Error Code The multiple controller displays error code when there is error of the ven...