Cooper & Hunter CHV-09MCC4W Operation Installation Maintenance Manual Download Page 10

4.2 Initial Check

To avoid any corrosive action to the heat 

exchangers, do not install the indoor unit in 

an acid or alkaline environment.

4.3 Installation

4.3.1 Opening of False Ceiling and Suspension Bolts

͓

Install the indoor unit in a space for easy operation 

and maintenance as shown in Fig. 4.1. 

Provide a service access door near the unit 

piping connection area on the ceiling.

Check to ensure that the ceiling is strong 

enough to hang the indoor unit.

Check if the ceiling surface is flat for the air 

panel installation.

(1) Select appropriate location and direction for installation

of indoor unit, and determine its location. Pay careful

attention to the space for the piping, wiring and

maintenance.

Fig. 4.1 Space around Indoor Unit

͓

The indoor unit must be installed at an appropriate
location so that the indoor temperature can be evenly
distributed.

͓

There should be no obstruction of air flow at the vent.

͓

Select the installation location as follows:
(A) Minimum Space
(B) Down Slope Pitch of Drain Pipe: 1/25~1/100

Do not install the indoor unit in a machinery shop 

or kitchen where vapor from oil or its mist flows 

to the indoor unit.

Once the oil deposits on the heat exchanger, it 

may impair the performance of indoor unit and 

cause damage to plastic parts therein.

Pay attention to the following points when the 

indoor unit is installed in a hospital or other 

facilities where there are electronic waves from 

medical equipment, etc.

͓

͓

(A) Do not install the indoor unit where the

 electromagnetic wave is directly radiated to the  

 electrical box,  remote control cable or remote 

 control.

(B) Install the indoor unit and components as far as

 practical or at least 

9.8ft.(

3m

)

 from the 

      electromagnetic wave radiator. 

(C) Install the remote control switch in an iron box.

Arrange the remote control cable in an iron

tube. Ground the iron box and iron tube.

(D) Install a noise filter when the power supply emits

harmful noises.

Fig. 4.2 Installation Location of Indoor Unit

Fig. 4.3 Opening of False Ceiling and Suspension 

Bolts

(3) Ensure that the ceiling is horizontally level;

otherwise, proper drainage flow would  be impossible.

(4 

    ) Strengthen the opening parts of the ceiling. 

(5) Mount suspension bolts, as shown in the figure.

͓
͓
͓

Drain Pipe

1/25~1/100 Down Slope

2

Piping Connection

Service Access 

Door ≥ 

23 32 .(

mm)

Service Access 

Door ≥ 

23 32 .(

450

mm)

Piping Connection

Piping Connection

Service Access 

Door ≥ 

23 32 .(

mm)

Distance from Wall Side

Service Space

Piping Connection

2

2 32 .(

10~20 mm

)

9 2

.(

2

60

 mm

)

2

2

.(

310 mm

)

Indoor Unit Height in Ceiling

● The figure on the right shows the sensing area of

motion detector when the motion detector in

panel is in service.

Motion detector

2.6ft.(0.8m) above the ground

   

Approx. 

9. ft.(

6m

)

Approx. 

28.9ft.(

m

)

 

     

 

 

 

 

a

   

 

  

8.2ft.(

2.5

m)

. ft.(

m)

29 9

(

)

Suspension Bolts

4 location of Suspension Bolts

299(

760

)

(Dimension 

of Suspension 

Bolts) 

33(

840

 

(Dimension of

 Indoor Unit) 

860-910

 (Dimension of Opening )

 

 

0   

( )

 

 

 

   

 

 

   

 

 

 

 

 

   

   

 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

≥9.8

ft

.

(

3

m) 

4.9ft

.

(1.5m) 

4.9ft

.

(1.5m) 

≥ 29 32 .

(

m

m) 

3

.(

mm)

3

.(

mm)

9

.(

mm)

9

.(

mm)

39 3 8 .(

mm)

m

m t

2 32(2 )

2 32(2 )

232(2)

232(2)

(Dimension of Suspension Bolts) 

.(mm)

( m

f

)

33

3

3

(8

9 )

33

(8 )

( m

f d

t)

4.9ft

.

(1.5m) 

Summary of Contents for CHV-09MCC4W

Page 1: ...NDITIONER PLEASE READ AND UNDERSTAND THIS MANUAL BEFORE USING THE AIR CONDITIONER KEEP THIS MANUAL FOR FUTURE REFERENCE 4 WAY CASSETTE TYPE ORIGINAL INSTRUCTIONS CHV 09SCC4W CHV 12SCC4W CHV 15SCC4W CH...

Page 2: ......

Page 3: ...at pump air conditioner within this range Do not have the air outlet directly faced towards animals or plants since this may bring about an adverse effect thereon The installation and service engineer...

Page 4: ...imals damaging the wiring and electrical components Bitten unprotected parts may cause a fire Firmly fix the connection wires The external force of terminal may result in looseness of terminal that ma...

Page 5: ...responsible for any consequence arising from the modification to equipment without our written consent 03257 17 127 Correct Disposal of this product This marking indicates that this product should not...

Page 6: ......

Page 7: ...Materials 5 2 Piping Connection 8 Test Run 9 Protection Control Devices 10 Field Operation Electrical Wiring 7 1 General Check 7 2 Wiring 7 3 Field Wire Size for Power Source Line 2 4 5 6 Drain Pipe...

Page 8: ......

Page 9: ...e etc may occur 87 21 Be careful not to cause damage to insulation materials of the unit surface when it s lifted 7RROV QVWUXPHQWV IRU QVWDOODWLRQ QVWDOODWLRQ RI QGRRU 8QLW Transport the product as cl...

Page 10: ...unit where the electromagnetic wave is directly radiated to the electrical box remote control cable or remote control B Install the indoor unit and components as far as practical or at least 9 8ft 3m...

Page 11: ...asher Suspension Bolt Suspension Bracket Water Pan Fig 4 6 Mounting Nuts and Washers Suspension Bolt Field Supplied Nut Field Supplied Insulating Washer Accessory Bracket for Fixing Indoor Unit Washer...

Page 12: ...ctors between the indoor unit and air panel Flange Surface Indoor Unit Bottom View Ceiling Indoor Unit Surface of Suspended Ceiling Suspension Bolt Surface of Ceiling Indoor Unit Bolt M6 Pattern Board...

Page 13: ...nance Manual for outdoor unit Excessive and inadequate refrigerant is a leading cause of system anomaly Please inject the right amount of refrigerant Pipe Size mm Tightening Torque ft N m 10 3 13 3 14...

Page 14: ...e drain pipe connection is shown 2 Prepare a polyvinyl chloride pipe with a 32mm outer diameter 3 Fasten the tubing to the drain hose with the adhesive agent and the factory supplied clamp The drain p...

Page 15: ...p the wires with adhesive tape or other materials and plug the wiring connection hole with seal material to protect the product from any condensate water or insects The electrical box entrance hole sh...

Page 16: ...Amps A MOP Max Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load Amps A Connecting Hole for Power Supply Wiring Connecting Hole for Communication Cables and Wire Controller Ca...

Page 17: ...ot operate the system until the electrical leakage is found and repaired B Check to ensure the stop valves of outdoor unit are fully opened and then start the system C Check to ensure the switch on ma...

Page 18: ...ls 1 and 2 of TB2 the PCB fuse will be blown In such a case it s essential to correct the wiring and then to set switch No 1 to ON position Note Symbol indicates the location of DIP switch The positio...

Page 19: ......

Page 20: ...3DFNLQJ LVW Details Remarks 1 Set 1 pc pc pcs pc 1 pc 6 pcs 2 pcs 1 pc 1 pc 1 pc Indoor Unit Operation Installation Maintenance Manual Pipe Clamp 1 pc 08 20 V01...

Reviews: