4. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
●
Instant energization afte de-energization while the capacitordischarges slowly?
●
The zero-cross detectioncircuit of the mainboard isdefined abnormal?
Malfunction diagnosis process:
Turn power off for
1minute,the turn
back on
The unit returns to normal.
Conclusion:U8 is displayed due to
power off/on while the
capacitor discharges slowly.
U8 is still
displayed
The zero-cross detection circuit
of the mainboard is defined
abnormal.Replace the mainboard
with the same model
Yes
No