CoolAutomation SMT-131 Manual Download Page 5

 
Page 5 
 

Take  care  to  ensure  excess  wiring  is  not  trapped  between  the  cases 

half’s  when  closing 

-  push 

excess wires into the wall cavity. Never press on the LCD when closing the SMT-131 as it may crack. 
Always press on the SMT-131 plastic case only.

 

 

DIP Switch Settings 

 

Switch 

Function 

On 

Off 

Sw1 

Indoor Fan Mode 

3 Fan Speed 

1 Fan Speed 

Sw2 

Equipment Type 

Heat Pump 

Heat Cool 

Sw3 

HP Mode (Sw2= ON) 
HC Mode (Sw2=OFF) 

Rev Valve Heat (B) 
HE 

 Fan With Heat 

Rev Valve Cool (O) 
HG 

 No Fan In Heat 

Sw4 

2 / 4 pipe mode 

2 pipe mode 

4 pipe Mode  

Sw5 

Comp Protection Delay 

5 Min Anti Cycle 

Immediate Comp start 

Sw6 

Klixon (Ricardo) Mode 

On 

Off 

Sw7 

Ventilation Mode 

Permitted 

Not Permitted 

Sw8 

Door Station (Optional) 

Fitted 

Door Station Not Used 

 
Note:    The  SMT-131  reads  the  switch  settings  on  power  up  only.  If  you  change  any  DIP  switch 
settings you must power cycle before these changes will take effect. 
 
It  is  expected  that  only  qualified  people  will  make  adjustment  to  these  dip  switch  settings. 
Knowledge  of  the  HVAC  system  under  the  control  of  the  SMT-131  is  essential  prior  to  making 
adjustment to these DIP switch settings.  
 

Caution

 

Incorrect adjustment of these DIP switch settings could cause HVAC equipment 

damage. This would NOT be covered by warranty. 

 

Wiring 

 HVAC Control   

Terminal Designations 

 

Terminal 

Function 

24V Neutral 

24V Active -  This voltage is switched back through the relays 

Hi 

Indoor Fan High Speed (

NOT

 

Used

 in Single fan speed mode -  Sw 1 = OFF) 

Med 

Indoor Fan Medium Speed (

NOT Used

 in Single fan speed mode -  Sw 1 = OFF) 

Low 

Indoor Fan Low Speed (Used in single & three fan speed mode) 

Compressor or Cool - (Based on Sw 2 setting) 

W - O/B 

Reversing Valve or Heat - (Based on Sw 2 setting) 

A1 

 Cool 

0-10V Output for Cooling (Typically used to control modulating valves) 

A2 

 Heat 

0-10V Output for Heating (Typically used to control modulating valves) 

A3 

 Fan 

0-10V Modulating Output for Indoor DC Fan 

Com 

 0V 

0V terminal - Used for 0-10V, sensor or digital inputs ground reference  

Modbus Data A 

Modbus Data B 

SI 

Remote temperature sensor input  (Remote / average / Modbus data use) 

DI 

Digital (Switched input) for forced un-occupied or initiate doorbell function 

WC 

Window Contact - Forces SMT-131 OFF if window open > 5 min (Adjustable) 

DS 

Door Switch 

 Monitors room door status for occupancy detection 

(see page 11)

 

PIR 

PIR (Movement sensor) input for occupancy detection (see page 11) 

Summary of Contents for SMT-131

Page 1: ...SMT 131 Manual Ver 2 6 1 6 18 ...

Page 2: ...in version 3 03 Firmware Version 2 5 Added Fan Relay lock to 0 10 outputs function Firmware Version 40 2 Version 2 6 Added Sensor Speed response Sensor Calibration Firmware 40 4 Index Index 2 Introduction 3 Thermostat operation 3 Installation HVAC Control 4 DIP Switch Settings 5 Wiring HVAC Control 5 Terminal Designations 5 0 10v Outputs 7 Belimo 6 Way Valve 8 2 Pipe Mode 8 Ancillary Functions 9 O...

Page 3: ... operate and has been designed to not require a user manual The diagram to the left shows all LCD elements and the 7 buttons Up Down Make Up Room Do Not Disturb On Off mode Fan Mode Deg C F Select Depending on switch and installer menu settings not all LCD segments or buttons maybe shown On Off Mode Tap the On Off button to turn the thermostat On or Off and if permitted to select heat only or cool...

Page 4: ...ply wish this data to be presented to Modbus Installation HVAC Control System Design Great effort has been taken to make the SMT 131 system intuitive reliable and easy to install Using a common sense approach to the installation will ensure this product is installed easily and to the customer s satisfaction Please read and understand this instruction manual so that installation testing and commiss...

Page 5: ...nt to these DIP switch settings Caution Incorrect adjustment of these DIP switch settings could cause HVAC equipment damage This would NOT be covered by warranty Wiring HVAC Control Terminal Designations Terminal Function C 24V Neutral R 24V Active This voltage is switched back through the relays Hi Indoor Fan High Speed NOT Used in Single fan speed mode Sw 1 OFF Med Indoor Fan Medium Speed NOT Us...

Page 6: ...function The 24VAC applied to the SMT 131 R terminal is switch back through the 2A relays to the equipment Note the drawing provided here Caution Although the SMT 131 is a robust device wiring errors can potentially damage the thermostat Warranty does NOT cover this damage Take care when wiring 24V near sensor inputs or the Modbus communications terminals ...

Page 7: ...ON OFF relays the heating and cooling calls may have started slightly before indicated on the thermostat display This is true of the fan also A1 Cool This output is used to control a cooling valve A2 Heat This output is used to control a heating valve A3 Fan This output is used to control a variable speed fan or a variable capacity AC system If the fan mode is set to Auto speed the 0 10V output wi...

Page 8: ... C from set point The heating and cooling span can be adjusted independently to a maximum of full heating and full cooling 3 C from set point The output is linear Note When using Belimo mode both the A1 cool and the A2 Heat 0 10 output are used Both will provide the same output to the value The A3 fan output will remain unchanged and can be used to control a DC fan or other devices 2 Pipe Mode The...

Page 9: ...s to automatically control temperature set points The HOT 243 wall controller mounted in the hallway outside of the room provides feedback of the guests needs to housekeeping plus provides a convenient button to activate the SMT 131 internal door bell Regardless of the need to control conferential HVAC systems 2 or 4 pipe fan coils with modulating valves the SMT 131 has the necessary outputs to ac...

Page 10: ...6 for this setting When the WC terminal and the Com 0V terminal are joined the SMT 131 will alternate FLt with the current room temperature Register 32 will permit a time delay to be set after the fault signal is received if necessary to reduce false trips The fault indication has NO effect on thermostat function Door Switch The Door switch input DS is used by the SMT 131 for 3 functions 1 To dete...

Page 11: ...occupant to set their desired temperature and mode of operation Once the door is closed the SMT 131 will look for movement as detected by the PIR sensor wired to the PIR input If no movement is seen within the installer pre set seek time installer adjustable 1 to 15 minutes the SMT 131 will return to Un occupied mode where the users temperature and mode will be replaced with installer pre set valu...

Page 12: ... wired to a simple card reader or other 3rd party system that may be pre installed for room occupancy detection When the SMT 131 is in Un occupied Mode the display will go completely blank except for the words Unoccupied in the top left corner If the optional HOT 243 hall way panel is installed its display backlight will go out to let housekeeping know the room is empty Modbus register 40004 also ...

Page 13: ... and controls to be remotely supervised and adjusted from a central location if needed Modbus object data can be found on page 14 of this manual The SMT 131 uses a high powered Maxim chipset that will theoretically permit the connection of up to 255 devices on a single Modbus node RF noises and other interferences will reduce the real world permitted connections to a maximum of 150 200 in most cas...

Page 14: ...hermostat s performance as well as set energy conservation settings This menu is deliberately hidden and difficult to enter to discourage unauthorised tampering The information card provided in the SMT 131 box provides details on how to enter the SMT 131 menu If this is lost please contact Smart Temp or an authorised distributor for support Navigating Through the Installer Mode Settings The bottom...

Page 15: ...t 1 F 4 C F button shown on LCD 0 Off default 1 On 5 High temp set limit 5C 30C or 41F 86F 6 Low temp set limit 5C 30C or 41F 86F 7 Dead band 0C 5 0C or 0F 10 0F in 0 1C 0 1F steps Depending on Option 3 above Data format Dead band 10 8 Fan Purge Period 0 OFF 1 Fan purge 1 min 2 Fan purge 3 min 3 Fan purge 5 min 4 Fan purge 10 min 5 Heat only fan purge 1 min 6 Heat only fan purge 3 min 7 Heat only ...

Page 16: ... increments Data format hour 10 23 Un occupied heat Set point 0 OFF 5C 30C 41F 86F 0 5C 1F steps 24 Un occupied cool Set point 0 OFF 5C 30C 41F 86F 0 5C 1F steps 25 Un Occupied fan mode Fan 3 Speed mode 1 Low Auto default 2 Med Auto 3 High Auto 4 Low ON 5 Med ON 6 High ON 26 Backlight 0 On with button press Only Default ver 3 1 1 Always On high 2 Low when standby high when active Default ver 3 1 2...

Page 17: ...ps 40 Default Start Temp Version Ver 3 3 0 OFF default 15 35C or 59 86F 41 Beeper Version Ver 3 9 0 Off 1 On default 42 Fan Relay Lock Version 40 1 0 Off default 1 On This function locks the Fan relay logic to 0 10V outputs if enabled depending on other settings it may cause fan to start and run before heat or cool calls from the W Y relays 43 Thermostat response to changes in room Temperature Ver...

Page 18: ...e 69 5 x 46 3mm Backlight White LED Other Colours Available Upon Request Display Type STN Touch Panel Relay Rating 30V 1Amp Max 0 10V Output Load 10mA Max Control Range 5 C to 30 C 41 F to 86 F Memory Type Non Volatile Settings Do Not Require Battery Backup Communications Modbus RTU 4 8K 9 6K 19 2 K 1 Stop Bit 8 Data Bits 1 Start Bit No Parity Plastic ABS Poly Blend UV Stabilised and Fire Rated Wa...

Reviews: