Commands Reference
CoolMaster PRM
19
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
RESPONSE
Position in String
Example
Format
Description
0-2
109
NNN
Indoor unit Centralized Address
4-6
ON
ON or OFF
On/Off Status
8-10
23C
NNC***
Set Temperature ºC
12-17
24,08C
NN,NNC***
Room Temperature ºC
20-23
Auto
Low,Med,High,Auto,Top
Fan Speed
25-28
Cool
Cool,Heat,Fan,Dry,Auto
Auto,Bps,HExc
AutC,AutH
Operation Mode
30-31/32/33
OK
OK or Xn, Xnn, nnnn
OK or Failure code
33/34/35
0
0 or 1
Filter Reset Sign present
* - See
** - See
*** - In Fahrenheit mode Temperature is printed as NNNF, see example below:
101 ON 101F 057F Low Cool OK 0
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
CoolMaster 1000D
v 0.3.1
CoolMaster 2000S
any
CoolMaster 3000T
any
CoolMaster 4000M
any
CoolMaster 6000L
any
CoolMaster 7000F
any
CoolMaster 8000I(MH)
any
CoolMaster 9000H
any
CoolMaster G
any
SEE ALSO
CoolMaster 4000M
4.1.17 stat3,stat4
SYNOPSIS
stat3 [UID]
stat4 [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units. stat3 compared to stat2 has no fractional part in the
room temperature presentation. stat4 compared to stat3 has additional THERMOSTAT_ON column.
EXAMPLE
>stat3
100 ON 12C 12C High Cool OK 0
101 OFF 32C 04C Low Dry OK 1
102 ON 07C 08C High Dry OK 0
OK
>stat4