Centrifugal Roof and Wall Exhausters

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

This publication contains the installation, operation

and maintenance procedures for standard units of the
VCR/VCRD/VCR-HP/VCRD-HP/VCR-XP/VCRD-XP -
Centrifugal Roof and Wall Exhausters
. Carefully read
this publication prior to installation or maintenance
procedure.

Loren Cook catalog, 

VCR

, provides additional informa-

tion describing the equipment, fan performance, available
accessories and specification data.

For additional safety information, refer to AMCA publica-

tion 410-96, 

Safety Practices for Users and Installers of

Industrial and Commercial Fans

.

All of the publications listed above can be obtained from

Loren Cook Company by phoning (417)869-6474, exten-
sion 166; by FAX at (417)832-9431; or by e-mail at
[email protected].

For information and instructions on special equipment,

contact Loren Cook Company at (417)869-6474. 

Receiving and Inspection

Immediately upon receipt of a VCR fan, carefully inspect

the fan and accessories for damage and shortage.

• Turn the wheel by hand to ensure it turns freely and

does not bind.

• Record on the 

Delivery

Receipt

 any visible sign of

damage.

Handling

Lift the fan by the lifting lugs

provided under top cap. Never lift
by the shaft, motor or housing.

Storage

If the fan is stored for any

length of time prior to installation,
store it in its original shipping
crate and protect it from dust,
debris and the weather.

Installation

If the fan was delivered with the motor unmounted, see 

the maintenance sections for belt and pulley installation.

If the fan was purchased as a wall mount unit and a 

grease terminator or grease trough was not purchased, a 

WARNING

This fan has rotating parts. Safety precautions 

should be exercised at all times during installation, 
operation, and maintenance. 
ALWAYS disconnect power prior to working on fan.

1-1/16 inch diameter drain hole should be inserted on the 
bottom side of the unit for drainage.

Fan Installation

a. Ensure the fan discharge is a minimum 40 inches 

above the roof surface and a minimum of 10 foot from 
any building air intake in order to comply with NFPA 96. 

b. Minimum exhaust velocity in the duct should be 1500 

FPM in accordance with NFPA 96.

c. If the fan is installed on a surface that is not level, install 

the fan in a position that places the drain tube at the 
lowest position. 

d. Secure the fan to the roof curb at all four corners using 

a minimum of four anchor bolts, lag screws or other

    suitable fastener.

Personal Safety

Disconnect switches are recommended. Place

the disconnect switch near the fan in order that
the power can be swiftly cut off in case of an
emergency, and in order that maintenance per-
sonnel are provided complete control of the
power source. 

VCR

VCR

 

/

 

VCRD

Lifting Lugs

Summary of Contents for VCR

Page 1: ...If the fan is stored for any length of time prior to installation store it in its original shipping crate and protect it from dust debris and the weather Installation If the fan was delivered with the motor unmounted see the maintenance sections for belt and pulley installation If the fan was purchased as a wall mount unit and a grease terminator or grease trough was not purchased a WARNING This f...

Page 2: ... passing through the opening of a field wiring com partment Personal Safety Disconnect switches are recommended Place the disconnect switch near the fan in order that the power can be swiftly cut off in case of an emergency and in order that maintenance per sonnel are provided complete control of the power source Grease Terminator Installation Final Installation Steps a Ensure fasteners and setscr...

Page 3: ...h Speed interchange leads T11 and T12 Low Speed interchange leads T1 and T2 Both Speeds interchange any 2 line leads T3 T2 T1 T11 T12 T13 Low Speed Low Speed Low Speed High Speed High Speed High Speed L1 L2 L3 Motor Line Line Line Operation Pre Start Checks a Lock out all the primary and secondary power sources b Inspect and tighten fasteners and setscrews particu larly fan mounting and bearing fa...

Page 4: ...a tion During the inspections stop the fan and inspect as instructed below 30 Minute Interval Inspect bolts setscrews and motor mounting bolts Adjust and tighten as necessary 8 Hour Interval Inspect belt alignment and tension Adjust and tighten as necessary 24 Hour Interval Inspect belt tension Adjust and tighten as necessary Maintenance Establish a schedule for inspecting all parts of the fan The...

Page 5: ... should be obtained by firmly pressing the belt Refer to Figure 1 c Lock the motor plate adjustment bolts in place d Ensure pulleys are properly aligned Refer to Figure 2 Pulley Alignment Pulley alignment is adjusted by loosening the motor pul ley setscrew and by moving the motor pulley on the motor shaft Figure 2 indicates where to measure the allowable gap for the drive alignment toler ance All ...

Page 6: ...commended Puller Lisle No 45000 Sterling Wheel Puller This puller is avail able at most automotive parts retail outlets Wheel to Inlet Clearance The correct wheel to inlet clearance is critical to proper fan performance This clearance should be verified before initial start up since rough handling during shipment could cause a shift in fan components Refer to wheel inlet draw ing for correct overl...

Page 7: ... 6 Wheel Assembly Wheel Assembly Wheel Assembly 7 Base Base Base 8 Conduit Conduit Conduit 9 Isolator 4 Isolator 4 Isolator 4 10 Upper Post 4 Upper Post 4 Upper Post 8 11 Lower Post 4 Lower Post 4 Lower Post 8 12 Wind Band Wind Band Wind Band 13 Brace 4 Brace 4 Brace 8 14 Power Assembly Power Assembly Power Assembly 15 Shaft Shaft Shaft 16 Bearing 2 Bearing 2 Bearing 2 17 Drive Sheave Drive Sheave...

Page 8: ...ting from normal wear and tear To make a warranty claim notify Loren Cook Company General Offices 2015 East Dale Street Springfield Missouri 65803 4637 explaining in writing in detail your complaint and referring to the specific model and serial numbers of your fan Upon receipt by Loren Cook Company of your written complaint you will be notified within thirty 30 days of our receipt of your complai...

Reviews: