ALSPA PROFIBUS Field Bus Coupler
2. Specification
(09/06)
Technical Manual
Page 2-1
2. Specification
2.1
PROFIBUS Board Specification
2.1.1 Fieldbus
Capable of communication rates from 9600 bit/s to 12Mbit/s (1.5M
bits/s for MVS3007-4001 PROFIBUS board).
Automatic Baud rate
selection from the following list:
•
9,600
bits/s
•
19,200 bits/s
•
93,750 bits/s
•
187,500 bits/s
•
500K
bits/s
•
1.5M
bits/s
•
3M bits/s (MVS3007-4002 PROFIBUS board only)
•
6M bits/s (MVS3007-4002 PROFIBUS board only)
•
12M bits/s (MVS3007-4002 PROFIBUS board only)
2.1.2 PROFIBUS
Protocol
Implements the PROFIBUS-DP Fieldbus protocol according to DIN
19245.
2.1.3
Data Refresh Rate
Data is exchanged between the PROFIBUS Fieldbus module and
the drive's parameters every 10ms.
2.1.4
MVS3007-4001 board Data Volume
Cyclic Channel Receive:
•
1 control word (16 bit), and
•
5 reference demands (16 bit),
or,
•
2 control words (16 bit), and
•
4 reference demands. (16 bit).
1
If at any time the baud rate is changed in the PROFIBUS-DP master then it is
necessary to power cycle the drive for the change to be recognised by this module.