GB
55
D 482
459
Ø 490
1200
2100
Combustible roof
372
176
A 1166
173
B 1076
C 470
38
Air inlet Ø67
Ø150
250
445
706
250
826
Combustible wall
C 780
* We recommended the same side distance as to combustible walls to prevent discolouration of painted non-flammable walls.
900
900
295
556
613
100*
Fire-retardant wall of
brick or concrete
The minimum distance in front of
the stove opening to combustible
parts of the building or interior
decoration must be at least 1 m.
The dimension diagrams only
show the minimum permitted
installation distances for the
stove. When connecting to a steel
flue, also note the safety distance
requirements of the flue. The
safety distance between an un-
insulated flue and a combustible
part of the building should be at
least 450 mm.
Installation distances
WHEN INSTALLING TURNTABLE (OPTION)
the
following installation distances do not apply.
See the separate installation instructions for
turntable.
631
400
278
278
278
100
Combustible wall
A = height from floor to chimney
connection upwards
B = height from floor to c/c chimney
connection rear
C = height from floor to air inlet
D = height from floor to lower edge
of hatch
INSTALLATION DISTANCES
431
200*
700
1100
260
82*
Fire-retardant wall of
brick or concrete
Permitted area
for combustible
parts of the
building