GB
43
Check that the installation distances in the figures are maintained. When top connecting a steel flue please refer to
the relevant manufacturer’s installation instructions.
Observe the safety distances to combustible material that steel flues require.
The minimum distance in front of the stove opening to combustible parts of the building or interior decoration must
be at least 1 m.
750
500
155
455
16
150
250
350
450
50
150
250
350
Combustible wall
Fire-retardant wall of
brick or concrete
712
mi
n 300
mi
n 1000
496
Combustible roof
320
70
155
16
454
700
1100
Fire-retardant wall of
brick or concrete
88
552
47
Air inlet Ø67
Ø150
Indirect air supply through the external wall.
Supply of combustion air
Combustion air can be supplied via a duct from outside, or indi-
rectly via a vent in the outer wall of the room where the stove
is to be placed. The amount of combustion air that is used for
combustion is approx. 25m³/h.
HK
C 586W
Installation distances
INSTALLATION DISTANCES / SUPPLY AIR