Controlsoft CS-AC-1100-BK Installation Instructions Download Page 4

4

Test the Reader

Caution:

The “crossed out wheeled bin” logo on Controlsoft products indicates that this product 

should not be disposed of via the normal household waste stream.

To prevent possible harm to the environment or human health, please 

separate this product from other waste streams.  For further information, 

contact your local government office or the retailer where you purchased 

product.

This information only applies to customers in European Union. 

For other countries, please contact your local government to investigate 

the possibility of recycling your product.

Controlsoft UK  

 

      +44 (0)1451 844896   
      [email protected] 
      controlsoft.uk.support

Information on all our products can be found on our website www.controlsoft.com 

Step 5: Mount the Reader 

Mount the reader using the screws supplied.  To provide additional protection to the 

terminal blocks and rotary switch, we recommend that you seal around the reader 

using a mastic or similar sealant.

Step 6: Test

To ensure that the reader is operating correctly, check that:

1. 

The LED is flashing green (normal wait state).

 

2.  An ‘allowed card’ swiped at the reader causes a double beep and a solid green 

LED for approximately 3 seconds (allow state). 

3.  A ‘denied card’ swiped at the reader causes a double beep and a solid red LED 

for approximately 3 seconds (deny state).

• 

If the LED flashes orange, there is a communication problem to the ACU.  Check 

that the ACU is operating normally, that the reader is connected to the ACU and 

the power supply, and that the RS485 address is unique.

•  If the LED and/or buzzer remain on permanently, the reader is experiencing 

operational problems.  Check that the reader has adequate power and that it is 

correctly connected to the ACU.

Summary of Contents for CS-AC-1100-BK

Page 1: ...e device very easy to use The reader circuitry is encased in a durable waterproof resin making it suitable for both internal and external use Step 1 Prepare the installation The reader can be mounted against any surface and in any orientation A template is provided to mark the position of the required holes Drill the holes plug the mounting holes if required and feed the cable through the cable en...

Page 2: ...tion rotary switch marked 0 to F The table below shows how the switch position relates to the address 2 Set the RS485 Address Rotary Switch 0 1 2 3 4 5 6 7 8 9 A B C D E F RS485 Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 For further information on RS485 Bus Addressing please refer to the i Net Installation Instructions Always keep a record of the address used to avoid duplication C B A 9 8 6 5 ...

Page 3: ...ut we recommend using stranded cores as opposed to solid cores Note the RS485 and connections must be run on either side of the same twisted pair e g Green and White If the reader is at the end of the RS485 bus then a network termination resistor 120 ohms must be fitted between the RS485 and connection at the reader terminal blocks Step 4 Connect Power The reader requires 12Vdc power at 100 mA for...

Page 4: ...ader Mount the reader using the screws supplied To provide additional protection to the terminal blocks and rotary switch we recommend that you seal around the reader using a mastic or similar sealant Step 6 Test To ensure that the reader is operating correctly check that 1 The LED is flashing green normal wait state 2 An allowed card swiped at the reader causes a double beep and a solid green LED...