CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
- 5 -
4) Engine Start & Stop
4.1 The controller is manual and auto start capable.
4.1.1 Manual Start – With the key in the manual start position, a display message of “Press Enter to Start”
will appear. Pressing the Enter button will crank the engine. The engine is shut down by turning the
key to the Off position.
4.1.2 Auto Start - Single or Dual Float - USE TWO NORMALLY OPEN CONTACTS WHICH WHEN BOTH
ARECLOSED, THE CONTROLLER WILL START THE ENGINE. WHENTHE LOW FLOAT OPENS,
THE ENGINE WILL BE STOPPED.
5) Engine Speed Control (Throttle Control)
5.1 None
6) Engine Faults
6.1 Engine Faults - In the case of an engine parameter is measured outside of the normal operating range, the
control panel will shut the engine down by opening the run circuit. A red LED will illuminate above the LCD
display and the LCD will display a text message describing which shutdown occurred.
6.1.1 Low Oil Pressure - Engine shutdown if below 15 PSI for 5 seconds.
6.1.2 High Engine Temperature – Engine shutdown if above 235 degrees F for 5 seconds.
6.1.3 Over Speed – Engine RPM is above 2550 for 1 second.
6.1.4 Low Fuel Level – Fuel Level is measured below 1% for 5 seconds.
7) Controller Specific Alarms
7.1 The controller monitors additional “system” inputs directly including:
7.1.1 Emergency Stop (Digital) - An Emergency Stop button can be attached to Term 12 on the control
board. Use a normally open button, which closes to ground. A shut down will occur when active.
7.1.2 Fuel Level Sender (Analog) - A Fuel Level Sender can be attached to Term 7 on the control board.
Use a 240 to 33 ohm scale for a 0 to 100% display. Attaching a fuel sender will automatically change
the LCD to display Fuel Level. A pre alarm is programmed at 20%. A shutdown is programmed at
1%.
7.1.3 Low Water Level Switch (Digital) - A Low Water Level switch can be attached to Term 5 on the control
board. Use a normally open switch, which closes to ground. A shut down will occur when active.
7.1.4 Low Oil Level Switch - A Low Oil Level switch can be attached to Term 6 on the control board. Use a
normally open switch, which closes to ground. A shut down will occur when active.
7.2 In the case of a fault, the engine will be shut down, the red LED will illuminate and a message will appear on
the digital display defining the specific shutdown condition.
7.3 To clear alarms, it is necessary to eliminate the cause of the alarm and cycle power to the controller (turn off
and back on).