DIAGNOSTIC - ALARM FUNCTIONS

LEDs 

behaviour

Error

Actuator use

Actuator behaviour

Typical trouble 

shooting condition

Reset 

procedure

Automatic calibration  

(DIP N. 7 OFF)

Manual calibration  

(DIP N. 7 ON)

1

RED ON

Valve stroke 

less than 

5mm

Calibration/

first 

installation

The actuator pushes/pulls 2 

times (unexpected stall) trying 

to remove the possible obstacle. 

After 2 tries an alarm is signalled 

and the actuator moves to initial 

position and does not respond to 

control signal. Stroke value is not 

updated because out of range

The actuator pushes/pulls 2 

times against endpoint during 

calibration and the actuator 

moves to the initial position and 

then it does not respond to the 

control signal. The actuator keeps 

the previous stroke

Valve with a stroke 

length lower than 

5mm

Remove 

power and 

power up 

again

2

RED quick 

bl 

GREEN ON

Stroke longer 

than 60mm

Calibration/

first 

installation

The actuator exits the 60mm 

stroke range and it moves toward 

the new stroke limit signalling an 

anomaly. The actuator pushes/

pulls 2 times against the new 

stroke limit, then it goes back to 

the initial position still signalling 

the anomaly until it is not within 

60mm. The actuator does not 

calibrate the stroke after 10s 

(wrong range)

The actuator exits the 60mm 

stroke range and it moves toward 

the new stroke limit signalling an 

anomaly. The actuator pushes/

pulls 2 times against the new 

stroke limit, then it goes back to 

the initial position still signalling 

the anomaly until it is not within 

60mm. The actuator does not 

calibrate the stroke after 10s 

(wrong range)

Valve with a stroke 

length longer than 

60mm

Remove 

power and 

power up 

again

3

RED Quick 

Blinking 

Unexpected 

stall 

within the 

calibrated 

stroke range

normal 

operation

The actuator tries 5 times against 

the new stall condition and then 

after 10s the actuator updates 

the new stroke length

The actuator tries 5 times against 

the new stall condition. At the 

end of the attempts the fault 

will be signalled. The actuator 

does not update the new stroke 

length, but after 60s makes 

other attempts to verify the stall 

condition

Valve stuck

Inverted 

control 

signal

4

RED Quick 

Blinking 

Stroke 

longer than 

expected

Normal 

operation

The actuator moves toward the 

new stall condition with a lower 

speed; after 10s the actuator 

updates the new stroke value

The actuator moves toward the 

new stall condition with a lower 

speed; after 10s the actuator 

does not update the new stroke 

value

Stem connection 

loose or valve 

damaged

Inverted 

control 

signal

5

RED slow 

Blinking

Low Power 

Voltage

Normal 

operation

The actuator is still working 

but performance cannot be 

guaranteed

The actuator is still working 

but performance cannot be 

guaranteed

1. Wrong 

transformer size

Correct 

Voltage 

Power

2. Unstable power

6

RED slow 

Blinking

High Power 

Voltage

Normal 

operation

The actuator is still working 

but performance cannot be 

guaranteed

The actuator is still working 

but performance cannot be 

guaranteed

1. Wrong 

transformer size

Correct 

Voltage 

Power

2. Unstable power

1

st

 Issue rev. b

04/2018

DBL564e

Page 6

Summary of Contents for MVE5-65 Series

Page 1: ...peration handle on the actuator When it is low ered manual override ON the power supply to the motor power stage circuitry is cut and the motor stops The actuator can be oper ated manually and the val...

Page 2: ...Modulating 5 15mm 15s Modulating 15 25mm 20s Modulating 25 60mm 30s Floating 60s Transformer Size VA 20 20 30 50 Stroke 5 60mm limited to 30mm for MVE5xxS 65 Force N 400 600 1000 1500 Duty cycle max 5...

Page 3: ...el To guarantee Nema Type 2 protection use flexible metal conduit not supplied Push the listed conduit fitting device over the actuator s cable to butt against the enclosure Screw in conduit connector...

Page 4: ...electronic components caused by the PCB bending do not press too much while fixing the terminal block WIRING DIAGRAMS 3 point floating control sink connection Controller 3 point floating control sink...

Page 5: ...rol 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON on...

Page 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Page 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Reviews: