Contents
Section
Description
Page
1.0
Description & Installation
2
2.0 Operation
3
3.0 Maintenance
5
4.0 Troubleshooting
5
5.0 Warranty
5
Pilot Pressure
Atmospheric Pressure
Supply Pressure
Output Pressure
441-622-015
Type 500X
Page 1
Electropneumatic Transducer (I/P, E/P)
Installation, Operation and
Maintenance Instructions
Type 500X
Ordering Information
Type 500X I/P Transducers
Output Range
Part Number
Input
psi
bar
Impedance
500-AA
4-20 mA
3-9
0.2-0.6
90 Ohms
500-AB
4-20 mA
9-15
0.6-1.0
90 Ohms
500-AC
4-20 mA
3-15
0.2-1.0
180 Ohms
500-AD
4-20 mA
3-27
0.2-1.9
220 Ohms
500-AE
4-20 mA
6-30
0.4-2.0
220 Ohms
500-AF
4-20 mA
1-17
0.1-1.2
250 Ohms
500-BC
10-50 mA
3-15
0.2-1.0
70 Ohms
500-BD
10-50 mA
3-27
0.2-1.9
85 Ohms
500-BE
10-50 mA
6-30
0.4-2.0
85 Ohms
500-AG
4-20 mA
2-60*
0.1-4.0
225 Ohms
500-AH
4-20 mA
3-120*
0.2-8.0
260 Ohms
500-BF
0-60 mA
2-120*
0.1-8.0
220 Ohms
Type 500X E/P Transducers
Output Range
Part Number
Input
psi
bar
Impedance
500-CC
0-5 VDC
3-15
0.2-1.0
615 Ohms
500-CD
0-5 VDC
3-27
0.2-1.9
530 Ohms
500-CE
0-5 VDC
6-30
0.4-2.0
530 Ohms
500-DC
1-9 VDC
3-15
0.2-1.0
985 Ohms
500-DD
1-9 VDC
3-27
0.2-1.9
840 Ohms
500-DE
1-9 VDC
6-30
0.4-2.0
840 Ohms
500-CF
0-5 VDC
2-60*
0.1-4.0
500 Ohms
500-EH
0-10 VDC
3-120*
0.2-8.0
805 Ohms
*Output shown is as calibrated at the factory. Large span adjustment capability
allows recalibration to achieve output ranges from 3-35 psig (0.2-2.4 bar) with
2-60 psig unit to 3-145 psig (2.0-10 bar) with 2-120 psig unit.
8 Columbia Drive / Amherst, NH 03031 USA
Website: www.controlair.com
Email: [email protected]
603-886-9400 FAX 603-889-1844
An ISO-9001:2008 Certified Company