5

Pilot Pressure

Atmospheric Pressure

Supply Pressure

Output Pressure

441-622-015

Type 500X

Page 1

Electropneumatic Transducer (I/P, E/P) 

Installation, Operation and  

Maintenance Instructions

Type 500X

Ordering Information

Type 500X I/P Transducers 

Output Range 

Part Number

Input

psi

bar

Impedance

 

500-AA

4-20 mA

3-9

0.2-0.6

90 Ohms 

500-AB

4-20 mA

9-15

0.6-1.0

90 Ohms 

500-AC

4-20 mA

3-15

0.2-1.0

180 Ohms 

500-AD

4-20 mA

3-27

0.2-1.9

220 Ohms 

500-AE

4-20 mA

6-30

0.4-2.0

220 Ohms 

500-AF

4-20 mA

1-17

0.1-1.2

250 Ohms 

500-BC

10-50 mA

3-15

0.2-1.0

70 Ohms 

500-BD

10-50 mA

3-27

0.2-1.9

85 Ohms 

500-BE

10-50 mA

6-30

0.4-2.0

85 Ohms 

500-AG

4-20 mA

2-60*

0.1-4.0

225 Ohms 

500-AH

4-20 mA

3-120*

0.2-8.0

260 Ohms 

500-BF

0-60 mA

2-120*

0.1-8.0

220 Ohms 

 

 

 

 

Type 500X E/P Transducers 

Output Range 

Part Number

Input

psi

bar

Impedance

 

500-CC

0-5 VDC

3-15

0.2-1.0

615 Ohms 

500-CD

0-5 VDC

3-27

0.2-1.9

530 Ohms 

500-CE

0-5 VDC

6-30

0.4-2.0

530 Ohms 

500-DC

1-9 VDC

3-15

0.2-1.0

985 Ohms 

500-DD

1-9 VDC

3-27

0.2-1.9

840 Ohms 

500-DE

1-9 VDC

6-30

0.4-2.0

840 Ohms 

500-CF

0-5 VDC

2-60*

0.1-4.0

500 Ohms 

500-EH

0-10 VDC

3-120*

0.2-8.0

805 Ohms 

 

 

*Output shown is as calibrated at the factory. Large span adjustment capability 

allows recalibration to achieve output ranges from 3-35 psig (0.2-2.4 bar) with  

2-60 psig unit to 3-145 psig (2.0-10 bar) with 2-120 psig unit.