SM-Universal Encoder Plus User Guide
www.controltechniques.com
Issue Number: 6
5
Installing the SM-Universal Encoder Plus
5.1
Solutions Module slots
There are three slots available, which the Solutions Module can be plugged into as
shown in Figure 5-1. The Solutions Module can be plugged into either one of these, but
it is recommended that slot 3 be used for the first Solutions Module then slot 2 and slot
1. This ensures maximum mechanical support for the Solutions Module once fitted.
Figure 5-1 Location of slots 1, 2 and 3 on the Unidrive SP
5.2
Installation
1.
Before installing the SM-Universal Encoder Plus in the Unidrive SP, ensure the AC
supply has been disconnected from the drive for at least 10 minutes.
2.
Ensure that both the +24V, and +48V backup power supplies are disconnected from
the drive for at least 10 minutes.
3.
Check that the exterior of the SM-Universal Encoder Plus is not damaged, and that
the multi-way connector is free from dirt and debris.
4.
Do not install a damaged or dirty SM-Universal Encoder Plus in the drive.
5.
Remove the terminal cover from the drive. (For removal / re-fitting instructions, see
Unidrive SP Solutions Module Installation Sheet
provided with the Solutions
Module
.
)
6.
Position the drive connector of the SM-Universal Encoder Plus over the connector
of the appropriate slot in the drive and push downwards until it locks into place.
Before installing the SM-Universal Encoder Plus, refer to Chapter 2
WARNING
Solutions Module
slot 1 (Menu 15)
Solutions Module
slot 2 (Menu 16)
Solutions Module
slot 3 (Menu 17)