![Control Techniques 0477-0008-01 User Manual Download Page 10](http://html.mh-extra.com/html/control-techniques/0477-0008-01/0477-0008-01_user-manual_2658670010.webp)
10
DeviceNet Module User Guide
www.controltechniques.com
Issue 1
6.
Parameter Object
The DeviceNet Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and
downloaded (read) using DeviceNet management software. When the DeviceNet Module is powered up, it automatically obtains
parameter information from the soft starter.
Table 6-1 Parameter object details
Detail
Value (Hex)
Comment
Class
0F
Parameter object address
Instance
1 to xxx
xxx = maximum soft starter parameter number
Attribute ID
01
Always 0x01
Get Service
0E
Read single soft starter parameter value
Set Service
10
Write single soft starter parameter value
NOTE
Only available on Digistart IS soft starters. For parameter details, see the soft starter User Manual.
7.
Specifications
Enclosure
Dimensions ........................................................................................................................... 35 mm (W) x 157 mm (H) x 90 mm (D)
Weight ..................................................................................................................................................................................... 250 g
Protection .................................................................................................................................................................................. IP20
Mounting
Spring-action plastic mounting clips (x 2)
Connections
Soft starter ......................................................................................................................................................... 6-way pin assembly
Network ................................................................................................... 5-way male and unpluggable female connector (supplied)
Maximum cable size ............................................................................................................................................................ 2.5 mm
2
Contacts ........................................................................................................................................................................... Gold flash
Settings
Node address (MAC ID)
Setting ............................................................................................................................................................. Rotary switches
Range ............................................................................................................................................. 0 to 63 (63, factory default)
Data rate
Setting ................................................................................................................................................................. Rotary switch
Options .......................................................................................................... 125 kB, 250 kB, 500 kB (125 kB, factory default)
Power
Consumption
steady state .................................................................................................................................................... 19 mA at 25 Vdc
......................................................................................................................................................................... 31 mA at 11 Vdc
in-rush (at 24 Vdc) .............................................................................................................................. 1.8 A maximum for 2 ms
Galvanically isolated
Certification
CE .......................................................................................................................................................................... IEC 60947-4-2
C
......................................................................................................................................................................... IEC 60947-4-2
Summary of Contents for 0477-0008-01
Page 20: ...20 Guide de mise en service Module DeviceNet www controltechniques com Indice 1 ...
Page 30: ...30 DeviceNet Modul Betriebsanleitung www controltechniques com Ausgabe 1 ...
Page 40: ...40 Guida dell utente del modulo DeviceNet www controltechniques com Versione numero 1 ...
Page 50: ...50 Guía del Usuario Módulo DeviceNet www controltechniques com Versión 1 ...
Page 60: ......