Document Ref: DV40APP / Rev 2 09/02/2010
Page 14 of 23
Raised by GG Checked_ _JBJ
Mains failed fault battery current:
1 Loop:
2 Loop:
3 Loop:
4 Loop:
145mA
170mA
195mA
220mA
Mains failed alarm battery current:
1 Loop:
2 Loop:
3 Loop:
4 Loop:
260mA
285mA
310mA
335mA
Battery charger type:
Adjustable 27.5V float charger.
Maximum battery charging
current:
1.5A
Battery type:
2 off 12V 12AH sealed lead acid standby battery
Battery size:
151mm x 98mm x 97.5mm
Panel inputs
Remote Fault:
Fully monitored circuit, 3k9 EOL, 680R active
Remote Evacuate:
Fully monitored circuit, 3k9 EOL, 680R active
Remote Silence:
Fully monitored circuit, 3k9 EOL, 680R active
Remote Reset:
Fully monitored circuit, 3k9 EOL, 680R active
Panel outputs
For each loop:
LO+
Loop out +ve
LO-
Loop out –ve
LI+
Loop ve
LI-
Loop return –ve
Alarm circuits
2 at 1A per circuit
Auxiliary supply:
18.8V-28V @ 500mA